background image

Troubleshooting

Thermo Scientific

Jewett Pass-Thru Blood Bank Refrigerators

         29

Chapter 9  

Troubleshooting

PROBLEM

POSSIBLE CAUSE

SOLUTION

The unit will not operate

Unit is not turned on

Flip the switch in the back of the unit to the "On" position and 
confirm light on switch comes on. 

Power cord unplugged

Plug unit into a grounded 3 prong outlet on a dedicated 

circuit

Power supply/Outlet is not 

working

Plug another electrical device into the outlet to confirm the 
outlet is receiving power. If the device does not work check 
and replace the building fuse or reset the circuit breaker. If 
problem continues call an electrician.

Building circuit breaker tripped

Reset breaker and plug unit into a grounded 3 prong outlet on 
a dedicated circuit

Power supply voltage incorrect

Verify power supply voltage matches unit voltage on 

dataplate

Unit warms up or 

temperature fluctuates 

(if unit is warming up 
remove product before 
troubleshooting to 

protect)

Door is open

Make sure door is completely closed and sealing properly

Warm product loaded into unit

Allow ample time to recover from loading warm product

Power supply/Outlet is not 

working

Plug another electrical device into the outlet to confirm the 
outlet is receiving power. If the device does not work check 
and replace the building fuse or reset the circuit breaker. If 
problem continues call an electrician.

Condenser is blocked or dirty

Clean condenser to ensure sufficient airflow

Airflow to machine 

compartment blocked

Maintain proper clearances around unit as described in 

“Installation” 

Airflow inside unit is blocked

Ensure aiflow path to grill inside freezer/refrigerator is clear 
and there is room for airflow around contents

Evaporator coil iced over

Look through grill inside unit to see if ice is blocking airflow 
through evaporator. If there is excessive ice turn unit off to 
defrost unit. Turn unit back on after ice is clear.

Cold or warm air from building 
HVAC system blowing directly on 
refrigeration system

Move unit out of HVAC airflow path

Troubleshooting table continued on next page

Summary of Contents for Jewett Pass-Thru BBR25D-1B

Page 1: ...Thermo Scientific Jewett Pass Thru Blood Bank Refrigerators Installation and Operation 326629H01 Revision B June 2014...

Page 2: ...All internal adjustments and maintenance must be performed by qualified service personnel Material in this manual is for informational purposes only The contents and the product it describes are subje...

Page 3: ...cation 4 9 Wiring 4 11 Chapter 5 Operation 5 13 Initial Startup 5 13 Performance 5 13 Defrost 5 13 Chapter 6 Installation and Removal of Drawers 6 15 Mounting Drawer Slides 6 15 Installation 6 16 Remo...

Page 4: ...Table of Contents 2 Jewett Pass Thru Blood Bank Refrigerators Thermo Scientific...

Page 5: ...ING A potentially hazardous situation which if not avoided could result in serious injury or death CAUTION A potentially hazardous situation which if not avoided may result in minor or moderate injury...

Page 6: ...system components especially the controller Use OEM exact replacement equipment or parts Before use confirm that the product has not been altered in any way Your unit must be properly grounded in conf...

Page 7: ...accessories for damage If unit or accessories have been damaged in shipping place a damage claim with the carrier If there is no exterior damage unpack and inspect the equipment within five days of d...

Page 8: ...Inspection for Damage 6 Jewett Pass Thru Blood Bank Refrigerators Thermo Scientific...

Page 9: ...age Frequency Current BBR55D 1B 120 V 60 HZ 12 A BBR55D 2A 230 V 50 HZ 6 1 A BBR25D 1B 120 V 60 HZ 9 A BBR25D 2A 230 V 50 HZ 4 5 A Not CE marked Packing List Inside the refrigerator is a bag containin...

Page 10: ...diagnostic use storage of samples not intended to be re introduced to the human body As a medical device for blood component storage use and possible re introduction to the human body Registration Thi...

Page 11: ...ure all doorways and passageways for clearance before moving cabinet These units will pass through a standard 30 x 84 door opening 2 Inspect the interior exterior and mechanical equipment for special...

Page 12: ...to prevent cord to metal contact Refer to the image below Note Do not position the equipment in direct sunlight near heating diffusers radiators or other sources of heat The ambient temperature range...

Page 13: ...are provided with all units WARNING For personal safety and trouble free operation this unit must be properly grounded before it is used Failure to ground the equipment may cause personal injury or da...

Page 14: ...Installation Wiring 12 Jewett Pass Thru Blood Bank Refrigerators Thermo Scientific...

Page 15: ...to operate within a 2 C to 4 C temperature range The refrigerator temperature will be shown on the digital display at the top of the unit Defrost The defrosting process initiates automatically in resp...

Page 16: ...Condensate Pan Operation Performance 14 Jewett Pass Thru Blood Bank Refrigerators Thermo Scientific...

Page 17: ...rigerators 15 Chapter 6 Installation and Removal of Drawers Mounting Drawer Slides 1 Push into slots in rear standard as shown in Step 1 Make certain that the opposite drawer slides are in the same sl...

Page 18: ...stallation 16 Jewett Pass Thru Blood Bank Refrigerators Thermo Scientific Installation 1 Place drawer on top of slides and push into rear stops 2 Align slot on lever with the tabs on the drawer slide...

Page 19: ...nd Removal of Drawers Removal Thermo Scientific Jewett Pass Thru Blood Bank Refrigerators 17 Removal 1 Lift lever up to unlock drawer from the drawer slides 2 Lift front of drawer up and pull clear of...

Page 20: ...Installation and Removal of Drawers Removal 18 Jewett Pass Thru Blood Bank Refrigerators Thermo Scientific...

Page 21: ...ear hinges gently press in on door so gasket sits firmly against cabinet face Tighten screws B 4 When adjustment is complete it hinges are adjusted so gasket seal is too tight door will tend to spring...

Page 22: ...s required and tighten screws B when adjustment is satisfactory No play will be present in the latch handle with the door closed 5 For in and out adjustment proper gasket seal loosen screw E Adjust in...

Page 23: ...the drawers shelves refer to Installation and Removal of Drawers The unit cooler fans need no lubrication The condensing unit needs no oil or other lubrication Annual inspection of the mechanical ref...

Page 24: ...ickly Failure to keep the condenser clean can result in equipment warm up or erratic temperatures WARNING Be sure to disconnect the unit from main power before cleaning the condenser CAUTION Never cle...

Page 25: ...rd the broken pieces refer Figure 1 Figure 1 Cover holding the broken bulb When replacing the bulb ensure that the light cover is put back on the CFL bulb in the unit refer Figure 2 Figure 2 CFL Bulb...

Page 26: ...ure The digital input can operate as fourth temperature probe The HOT KEY output allows to connect the unit by means of the external module XJ485 CX to a network line ModBUS RTU compatible such as the...

Page 27: ...ase during the Energy Saving cycle 30 0 Cy30 0 C 22 86 F it sets the increasing value of the set point during the Energy Saving cycle OTHER Adr Serial address 1 244 Identifies the instrument address w...

Page 28: ...2 C 120y120 F 0 Pr2 P4P Fourth probe presence n not present Y pres n Pr2 O4 Fourth probe calibration 12y12 C 120y120 F 0 Pr2 OdS Outputs delay at start up 0 255 min 0 Pr2 AC Anti short cycle delay 0 y...

Page 29: ...shooting to protect Door is open Make sure door is completely closed and sealing properly Warm product loaded into unit Allow ample time to recover from loading warm product Power supply Outlet is not...

Page 30: ...e some noise when running Keeping proper spacing to the wall and ceiling will help to minimize noise Condenser is blocked or dirty Clean condenser to ensure sufficient airflow Loose parts Check around...

Page 31: ...t turn on Light switch is off Turn light switch on Light bulb is burned out Replace light bulb with Philips PL C 13W 841 4P 314357H01 and install the light cover 314755H02 on the bulb Door switch is s...

Page 32: ...Troubleshooting 32 Jewett Pass Thru Blood Bank Refrigerators Thermo Scientific...

Page 33: ...o Description 7462TA Additional extra drawer 7464TA Shelf set for BBR25D models 5 shelves 7476TA Shelf set for BBR55D models 10 shelves 7465TA Additional shelf 7480TA Right hand hinge door non control...

Page 34: ...Accessories 34 Jewett Pass Thru Blood Bank Refrigerators Thermo Scientific...

Page 35: ...tizfizieren die unter diese RoHS Anweisungfallen finden Sie unter www thermo com Conformit WEEE Questo prodotto deve rispondere alla direttiva dell Unione Europea 2002 96EC in merito ai Rifiuti degli...

Page 36: ...36 Jewett Pass Thru Blood Bank Refrigerators Thermo Scientific...

Reviews: