background image

2

Thermo Scientific Revco Laboratory Refrigerators and Freezers

Installation and Operation

4

Installation

CAUTION!

Improper operation of the equipment 

could result in dangerous conditions. To preclude 
hazard and minimize risk, follow all instructions and 
operate within design limits noted on the dataplate.

4.1

Location

Install the unit in a level area free from vibration with a minimum 
of 1.5 inches of space on all sides.

Do not position the equipment in direct sunlight or near heating 
diffusers, radiators, or other sources of heat. The ambient 
temperature range must be between 60 and 90

°

F  (16 to 32

°

C).

4.2

Wiring

CAUTION!

Connect the equipment to the correct 

power source. Incorrect voltage can result in severe 
damage to the equipment.

DANGER!

For personal safety and trouble-free 

operation, this unit must be properly grounded before 
it is used. Failure to ground the equipment may cause 
personal injury or damage to the equipment. Always 
conform to the National Electrical Code and local 
codes. Do not connect unit to already overloaded 
power lines.

General purpose units use 15 or 20 amp power cords. They are 
rated for 115 volts, AC, 60 Hz. Do not use extension cords, and 
always use a three prong grounded wall outlet. Figure 1 shows 

standard NEMA service cord plugs and wall outlets used for 
refrigerators and freezers. 

Figure 1.  NEMA Plugs and Receptacles

4.3

Leveling

The unit must be level. Rotate the leveling screws, located under 
the front corners of the unit, until the unit is level. If the floor is 
seriously out of level, you may need to shim the corners with thin 

sheets of metal.

Note:

Use thin sheets of metal to level units equipped with 
casters.

4.4

Door Seal

To check the door seal, complete the following steps:

1. Open the door.
2. Insert a strip of paper (a couple of inches wide) between the 

door gasket and the cabinet flange and close the door.

3. Slowly pull the paper strip from the outside. You should feel 

some resistance.

4. Repeat this test at 4 inch intervals around the door. If the door 

does not seal properly, replace the gasket.

CAUTION!

Door seal integrity is critical for 

refrigerators and freezers. A loose fitting gasket allows 
moist air to be drawn into the cabinet, resulting in 
quicker frost buildup on the evaporator coil, longer 
running time, poor temperature maintenance, and 
increased operation cost.

5

Operation 

5.1

Temperature Control

Standard units have cold controls mounted inside the cabinet, 
except for some compact units that have the controls mounted in 
back of the cabinet. 

Start by setting the control one quarter turn clockwise from the 
Off position. (The Off position is as far as you can turn the knob 
counterclockwise.) Wait 24 hours before adjusting the setting 

again. The farther you turn the knob clockwise, the colder the 
setting.

Some compact models have digital displays and controls 

mounted inside the cabinet. For these models, adjust setpoint 
temperature using the 

WARMER

 and 

COLDER

 buttons.

5.2

Combination Refrigerator/Freezers

If your unit has separate refrigerator and freezer compartments, it 

is important to remember that the temperature sensor is located in 
the refrigerator compartment. If you find that your freezer is not 
cold enough, you should open the refrigerator door more 

frequently to initiate cooling cycles.

5.3

Defrosting

When frost in the freezer compartment exceeds

 ¼

”, turn the unit 

off and allow the ice to melt. Do not use an ice pick or other 

sharp object to dislodge the ice. You can speed defrosting by 
placing a pan of warm water in the freezer compartment after 
turning the unit off.

15A-115V

NEMA 5-15P

20A-115V

NEMA 5-20P

5-15R

5-20R

(accepts both

5-15P and 5-20P)

Summary of Contents for REVCO Series

Page 1: ...Installation and Operation Manual Thermo Scientific Revco General Purpose Flammable Storage and Explosion Proof Laboratory Refrigerators and Freezers...

Page 2: ...2007 Thermo Fisher Scientific All rights reserved Suva is a registered trademark of DuPont All other trademarks are the property of Thermo Fisher Scientific Inc and its subsidiaries...

Page 3: ...lation 2 4 1 Location 2 4 2 Wiring 2 4 3 Leveling 2 4 4 Door Seal 2 5 Operation 2 5 1 Temperature Control 2 5 2 Combination Refrigerator Freezers 2 5 3 Defrosting 2 6 Cleaning 3 7 Troubleshooting 3 8...

Page 4: ...uential damages regardless of the legal theory asserted including negligence and or strict liability Before using user shall determine the suitability and integrity of the product for the intended use...

Page 5: ...g steps 1 Open the door 2 Insert a strip of paper a couple of inches wide between the door gasket and the cabinet flange and close the door 3 Slowly pull the paper strip from the outside You should fe...

Page 6: ...Unit does not operate Power supply 1 Check that the cord is securely plugged in 2 Plug another appliance into the outlet to see if it is live 3 If the outlet is dead check the circuit breaker or fuse...

Page 7: ...and contents fully loaded 8 2 Electrical Requirements A properly grounded electrical receptacle must be installed to service this unit The minimum wire size is 12 AWG A circuit breaker or time delay...

Page 8: ...s Installation and Operation Figure 2 Field Wiring for Explosion Proof Units factory supplied junction box connections per local codes cover customer supplied compressor factory supplied seal fittings...

Page 9: ...zu identifizieren die unter diese RoHS Anweisungfallen finden Sie unter www thermo com Conformit WEEE Questo prodotto deve rispondere alla direttiva dell Unione Europea 2002 96EC in merito ai Rifiuti...

Page 10: ...information can be found on the dataplate attached to the equipment If available please provide the date purchased the source of purchase manufacturer or specific agent rep organization and purchase...

Page 11: ...Thermo Fisher Scientific Inc 275 Aiken Road Asheville NC 28804 United States www thermofisher com 68393H01 Rev G...

Reviews: