ProReact EN Analogue Cable Test Kit Instructions

Document Ref.  PACC-CTK

 Pro

React 

EN Analogue

Linear Heat Detection 

Sensor Cable Testing Instructions

Summary of Contents for ProReact EN Analogue

Page 1: ... www thermocable com Linear Detection Technology Made Simple Page 1 of 8 Revision 1 0 Mar 2020 ProReactENAnalogueCableTestKitInstructions DocumentRef PACC CTK ProReactENAnalogue LinearHeatDetection SensorCableTestingInstructions ...

Page 2: ...ar 2020 ProReactENAnalogueCableTestKitInstructions DocumentRef PACC CTK Contents ProReact EN Analogue Sensor Cable Test Kit Page 3 Overview Kit Contents Technical Information Operating Instructions Page 6 Troubleshooting Page 8 ...

Page 3: ...have been made accessible during the system design and installation as per the manufacturer s recommendations A functional test is straightforward to be undertaken and a test kit can be re used where necessary Kit Contents Each ProReact EN Analogue Sensor Cable Test Kit A1900 contains Part Code Product Description Quantity Spare part availability A1904 120V 240Vac to 50Vac Power supply unit 1 3 A1...

Page 4: ...chnicalInformation 120V 240Vacto50VdcPowersupplyunit Part No A1904 Part Description 120V 240Vac to 50Vac power supply unit Dimensions inc handle 185mm H x 160mm W x 260mm D Operating Temperature 0 C to 50 C Operating Humidity 0 to 90 RH Input Voltage 120V or 240Vac switchable Output Voltage 50Vac Max Input Current 1 5A Max Output Current 5A Figure 1 Power supply unit rear ...

Page 5: ...ture 40 C to 40 C Operating Humidity 0 to 99 RH Thermal Power Output Approx 15W m Part code Part Description Heated Length m A1901 ProMinder Red Cable for zone lengths between 50m 125m 3 6 A1902 ProMinder Blue Cable for zone lengths between 100 350m 10 2 A1903 ProMinder Brown Cable for zone lengths between 175m 500m 16 6 each cable includes 5m cold lead with plug on for connecting to power supply ...

Page 6: ...select ProMinder Brown cable 3 Locate a suitable section of sensor cable to attach the heating cable to A minimum of 1 of the sensor cable will need to be heated but for the best test results try and attach the heating cable to approximately 3 of the sensor cable For example if the zone length is 88m as previously calculated attach the ProMinder Red cable to 2 6m 3 of 88 metres section of sensor c...

Page 7: ... and instruction manual for guidance If the alarm temperature setting was changed always return the setting to the original value once the test is completed 13 Press the green Start button on the front panel of the power supply unit to start the test The green Start button will light up and the red Stop button light will turn off The power supply unit supplies power to the heating cable for approx...

Page 8: ...r does not move after the green button is pressed check the cable is attached correctly to the power supply unit Disconnect power to the power supply unit and check the fuse on the front panel see Figure 3 The fuse can be removed by twisting the fuse plug anti clockwise If the power supply unit red Stop button does not light up after connecting the unit to a mains supply Check the fuse on the main...