MULTIFUNCTIONAL UNITS RLC – Installation and maintenance manual
MUMRLCHEAT_REV01_1012_UK
Pag. 30 di 31
16
Recommended spare parts
There follows a list of the recommended parts for several years’ running. Thermocold is at your disposal to recommend a personalised
list of accessories according to the commissioned order, including the part number of the equipment.
1 year
Components
Quantity
fuses
(all)
filter dryers
(all)
solenoid valves
(1 per type)
thermostatic valves
(1 per type)
pressostats
(1 per type)
pressure gauges
(1 per type)
contactors and relays (1 per type)
thermal protectors
(1 per type)
carter electric
heaters
(1 per type)
4-way valve
(1 per type)
check valve
(1 per type)
safety valve
(1 per type)
sight glass
(1 per type)
fans and engines
(1 per type)
2 year
Components
Quantity
fuses
(all)
filter dryers
(all)
solenoid valves
(all)
thermostatic valves
(all)
pressostats
(all)
pressure gauges
(all)
contactors and relays
(all)
thermal protectors
(all)
carter electric heaters
(all)
4-way valve
(1 per type)
check valve
(1 per type)
safety valve
(1 per type)
sight glass
(1 per type)
fans and engines
(1 per type)
electrical components
(all)
compressors
(1 per type)
5 year
Components
Quantity
fuses
(all)
filter dryers
(all)
solenoid valves
(all)
thermostatic valves
(all)
pressostats
(all)
pressure gauges
(all)
contactors and relays
(all)
thermal protectors
(all)
carter electric heaters
(all)
4-way valve
(all)
check valve
(all)
safety valve
(all)
sight glass
(all)
fans and engines
(all)
electrical components
(all)
compressors
(all)
heatexchanger
(1 per type)
17
Improper uses
The unit is projected and built up to grant the maximum safety in its proximity, as well as to resist to the aggressive environmental
conditions. The fans are protected by grilles.
Residual risks are indicated with warning labels.
SAFETY SYMBOLS
DANGER:
DANGER:
DANGER:
DANGER:
General danger
Temperature Moving parts Cut off voltage
18
Disposal
18.1
Unit disconnection
Only qualified personnel can dispose the unit.
Pay attention not to evacuate in liquid or dangerous gas spaces.
Recover the refrigerant gas of the unit and unfrozen solutions in the idraulic circuit.
18.2
Disposal
Exchangers, condensing coi fins, ventilators or motors could be retrieved if they are still operative.