1/16 & 1/32 DIN TEMPERATURE CONTROLLER  
MANUAL (59423-5) 

 

MECHANICAL INSTALLATION 

 

The Controllers are designed to be mounted either in a 1/16 or a 1/32 DIN panel cutout. The units are sleeve mounted with the front 
bezel assembly rated NEMA4/IP66 provided that: 

 

the panel is smooth and the panel cutout is accurate; 

 

the mounting instructions are carefully followed. 

 

DIN PANEL CUTOUT 

1/16 DIN

: 45.0mm +0.6 / 0.0 wide, 45.0mm +0.6 / 0.0 high 

1/32 DIN

: 45.0mm +0.6 / -0 wide, 22.2mm +0.3 / -0 high 

Maximum panel thickness 

9.5mm 

Minimum spacing 

20mm vertical, 10mm horizontal 

 

MOUNTING 

To mount a Controller proceed as follows: 

1 Check that the controller is correctly orientated and then slide the unit into the cutout. 
2 Slide the panel clamp over the controller sleeve pressing it firmly against the panel until the controller is held firmly. 
3 The controller front bezel and circuit board assembly can be unplugged from the sleeve. Grasp the bezel firmly by the recesses on 
each side and pull. A screwdriver can be used as a lever if required. 
4 When refitting the bezel assembly it is important to press it firmly into the sleeve until the latch clicks in order to compress the 
gasket and seal to NEMA4X/IP66. 

 

CLEANING 

Wipe down with damp cloth (water only) 

Note: 

The controller should be isolated before removing or refitting it in the sleeve, and electrostatic precautions should be observed 

when handling the controller outside the sleeve. 

 

DIMENSIONS: MODELS 

 

Model Bezel

*

 Behind 

panel 

Overall 

length 

Behind panel 

length

*

 

Width Height  Width 

Height 

1/32 DIN – 48 x 24mm 

51.0 

28.5 

44.8 

22.0 

116.2 

106.7 

1/16 DIN – 48 x 48mm 

51.0 

51.0 

44.8 

44.8 

116.2 

106.7 

 

ELECTRICAL INSTALLATION 

(Also see important Safety Information)

 

 
OUTPUT DEVICES 

Two of the following output devices are fitted to the controllers, depending on the model. 

1 Solid state relay drive (SSd/SSd1/SSd2) 

5Vdc +0/-15%, 15mA non isolating

To switch a remote SSR (or logic)

 

2 Miniature power relay (rLY/rLY1) 

2A/250V AC resistive, Form A/SPST contacts. 

3 Sub miniature power relay (rLY2) 

1A/250V AC resistive, Form A/SPST contacts. 

 

OUTPUT DEVICE ALLOCATION 

Any of the available outputs may be chosen for the main setpoint (SP1), the remaining device being automatically allocated to the 
second setpoint (SP2). 
 

Dual relay or dual SSd output models are available to order. Please contact your local distributor for details. 

 

Designed for use with the following supply voltages: 
1). 100 - 240V 50-60 Hz 4.5 VA (nominal) +/-10% maximum permitted fluctuation 
2). 12V - 24V (AC/DC) +/-20% 4.5 VA Polarity not required 
 
The supply voltage is dependant on the specific model, check the product label to establish the correct voltage for the unit.  
 

WIRING THE CONNECTOR 

Prepare the cable carefully, remove a maximum of 8mm insulation and ideally tin to avoid bridging. Prevent excessive cable strain. 
Maximum recommended wire size: 32/0.2mm 1.0mm

(18AWG). 

 

INDUCTIVE LOADS 

To prolong relay contact life and suppress interference it is recommended engineering practice to fit a snubber (0.1uf/100 ohms) 
between terminals 5 and 6. 

 
CAUTION:Snubber leakage current can cause some electro-mechanical devices to be held ON.  
Check with the manufacturers specifications. 

 

EN61010 - /CSA 22.2 No 1010.1 92 

  Compliance shall not be impaired when fitted to the final installation. 

  Designed to offer a minimum of Basic Insulation only. 

  The body responsible for the installation is to ensure that supplementary insulation suitable for Installation Category II or III is 

achieved when fully installed. 

  To avoid possible hazards, accessible conductive parts of the final installation should beprotectively earthed in accordance with 

EN6010 for Class 1 Equipment. 

  Output wiring should be within a Protectively Earthed cabinet. 

  Sensor sheaths should be bonded to protective earth or not be accessible. 

  Live parts should not be accessible without the use of a tool. 

  When fitted to the final installation, an IEC/CSA APPROVED disconnecting device should be used to disconnect both LINE and 

NEUTRAL conductors simultaneously. 

  A clear instruction shall be provided not to position the equipment so that it is difficult to operate the disconnecting device. 

 

SENSOR SELECTION 

Thermocouples Description 

Sensor Range 

Linearity 

tC b 
tC E 
tC J 
tC K 
tC L 
tC n 
tC r 
tC s 
tC t 

Pt-30% Rh/Pt-6%Rh 
Chromel/Con 
Iron/Constantan 
Chromel/Alumel 
Fe/Konst 
NiCrosil/NiSil 
Pt-13% Rh/Pt 
Pt-10% Rh/Pt 
Copper/Con 

0 to 1800°C 
0 to 600°C 
0 to 800°C 
-50 to 1200°C 
0 to 800°C 
-50 to 1200°C 
0 to 1600°C 
0 to 1600°C 
-200 to 250°C 

2.0* 
0.5 
0.5 
0.25* 
0.5 
0.25* 
2.0* 
2.0* 
0.25 

Resistance Thermometer RTD 

Pt100/RTD-2 

-200 to 400°C 

0.25* 

 
Linear process inputs (Input mV range: 0 to 50mV) 
Displays 0 - 20mV 4 - 20mV setpoint limits 
Lin1  

0 - 100 0 – 400 

 ± 0.5% 

Lin2  

0 - 100 -25 - 400  

± 0.5% 

Lin3  

0 - 1000 0 - 3000  

± 0.5% 

Lin4  

0 - 1000 -250 - 3000  

± 0.5% 

Lin5  

0 - 2000 0 - 3000  

± 0.5% 

Notes:  

1 Linearity: 5-95% sensor range  
2 * Linearity B:5° (70º - 500°C) K/N:1° >350°C exceptions: R/S: 5°<300°C T:1° <- -25° >150°C  
RTD/Pt100: 0.5° <-100°C 

CONNECTION DIAGRAM 

 

 

 

SAFETY INFORMATION 

 
INSTALLATION

   

 

Designed for use: 
UL873 - only in products where the acceptability is determined by Underwriters Laboratories Inc. 
EN61010-1 / CSA 22.2 No 1010.1 - 92 
To offer a minimum of Basic Insulation only. 
Suitable for installation within Category II and III and Pollution Degree 2. 
SEE ELECTRICAL INSTALLATION It is the responsibility of the installation engineer to ensure this equipment is installed as 
specified in this manual and is in compliance with appropriate wiring regulations. 

 
CONFIGURATION

 

All functions are front selectable, it is the responsibility of the installing engineer to ensure that the configuration is safe. Use the 
program lock to protect critical functions from tampering. 

 

ULTIMATE SAFETY ALARMS 

Do not use SP2 as the sole alarm where personal injury or damage may be caused by equipment failure. 

 
INSTRUMENT PANEL FEATURES

 

 

 
Green Display: 

Process temperature or program 

Function/Option

 

Orange Display: 

Setpoint temperature or program 

Option (Dual Display only)

 

Green LED: 

Setpoint 1 output indicator 

Red/Orange LED: 

Setpoint 2 output indicator 

 

 

ADJUSTMENTS 

To enter or exit 

program mode

: Press 

 

 together for 3 seconds 

To scroll through 

functions

: Press 

 or 

 

 

To change 

levels 

or 

options

: Press 

 

 together or 

 

 

together 

To view setpoint: Press 

 

To increase setpoint: Press  

 

 together 

To decrease setpoint: Press 

 

  together 

To reset an alarm or fault condition: Press 

 

 together briefly 

Notes: 

If in difficulty by becoming “lost” in program mode, press 

 and 

 together for 3 seconds to return to 

display mode, check the INSTRUMENT ADJUSTMENTS above and try again. 
 
When in program mode, after 60 seconds of key inactivity the display will revert to either 

inPt : nonE 

or, if the 

initial configuration has been completed, the measured value. Any settings already completed will be retained. 

 

GETTING STARTED 

 
After power-up the controller requires programming with the following information: 

 

Type of Sensor 

 

 

Operating unit 

 

 

Allocation of Output Device to SP1/SP2 

(Relay or SSd) 

 

Temperature Setpoint 

 
When the above information has been programmed into the controller it will be operational with the following factory settings. 

 
P

roportional band/Gain  

 

10ºC/18ºF 

I

ntegral time/Reset  

 

5 mins 

D

erivative time/Rate  

 

25 secs 

Proportional cycle-time  

 

20 secs 

(Typical setting for relay output) 

DAC Derivative approach control  

1.5 

(Average setting for minimum overshoot) 

 
NOTE: The instruments covered in this manual may be fitted with either a single or a dual display. Where a single display 
shows more than one reading, it will alternate between them. 

 

INITIAL SET-UP 

On power-up the controller will display the self test sequence followed by the initial display 

inPt : none

 

 Select input sensor.

 

 

Press and hold 

 

and use the 

 

or 

 

 

buttons to scroll through the sensor selection list until the correct sensor is 

displayed. Release the buttons. The display will now read selected sensor type e.g. 

inPt : tCs

 

 

Press 

 

 

once 

The display will now read 

unit : none

 

 

Select unit. 

 

Press and hold 

 

and use the 

 

or 

 

 

buttons to scroll through the unit selection list until the correct unit is 

displayed. Release the buttons. The display will read selected unit e.g. 

unit : °C

 

 

Press

 

 

once 

The display will now read 

SP1.d : nonE

 

 

Select SP1 (Main setpoint output device) 

       

Note: Dual Relay and Dual SSd Output Options Models have their outputs pre-configured. Move to Step 4. 

 

Press and hold  

 

and use the 

 

or 

 

 

buttons to select 

SSd 

or 

rLY 

as required. The controller will now read 

selected output device e.g. 

SP1.d : SSd

 

 

To enter initial configuration into controller memory 

 

Press and hold 

both 

 

and 

 

 

buttons for 3 seconds. The display will now read 

ParK 

and measured variable 

(temperature) (eg. 

23 

ParK 

is displayed because a setpoint

 

has not yet been entered.

 

 

To display setpoint 

Press and hold 

  

 

The displays will now read 

unit 

(eg. 

°C 

) and 

0  

 

To enter setpoint 

 

Press and hold  

 

and use 

 

button to increase or 

 

button to decrease the reading and scroll to required setpoint 

value. (The digit roll-over rate increases with time). 

 

THE CONTROLLER IS NOW OPERATIONAL WITH FACTORY SETTINGS 

 
Note: 

For precise control of an application the controller may need to be TUNED. Please see the following section on AUTOTUNE 

 

AUTOTUNE 

This is a single shot procedure to match a controller to the process. Select either 

Tune 

or 

Tune at Setpoint 

from the criteria below. 

 
The 

Tune 

program should be used when the load temperature is at or near ambient. The procedure will apply disturbances when 

the temperature reaches 75% of the setpoint value, causing overshoot which is monitored in order to adjust the 

DAC 

overshoot 

inhibit feature. Care should be taken to ensure that any overshoot is safe for the process. 
 
The 

Tune at Setpoint 

program is recommended when: 

 

The process is already at setpoint and control is poor 

 

The setpoint is less than 100°C 

 

Re-tuning after a large setpoint change 

 

Tuning multi-zone and/or heat-cool applications. 

 
Notes

:  

DAC 

is not re-adjusted by Tune at setpoint. 

Proportional Cycle Time 

can be pre-selected before running the Autotune program.  

 

Hereafter the symbol (

▲▼

) signifies both buttons are held pressed for 3 seconds to ENTER or EXIT program mode. 

 

TUNE OR TUNE AT SETPOINT PROGRAM 

Enter program (

 

) and from the display 

tunE : oFF 

press and hold 

 

 

and press 

 

to display 

tunE : on 

or 

tunE : At.SP  

Exit program mode (

 

). 

 
The 

TUNE 

program will now start. The display will show 

tunE 

as the process temperature climbs to setpoint. 

Note: 

During tuning, the main setpoint (SP1) LED will flash. 

 
When the 

TUNE 

or 

TUNE AT SETPOINT 

program is complete the PID values are entered automatically. The process temperature 

will rise to setpoint and control should be stable. If not, this may be because optimum cycle time is not automatically implemented. 
To set the cycle time see 

PROPORTIONAL CYCLE-TIME

 

PROPORTIONAL CYCLE-TIME 

The choice of cycle-time is influenced by the external switching device or load. eg. Contactor or SSR. A setting that is too long for a 
process will cause oscillation or a setting that is too short will cause unnecessary wear to an electro-mechanical switching device. 
 

Factory set - 

To use the 20 sec factory set cycle-time no action is needed whether autotune is used or not.

 

 
To Manually Select AUTOTUNE Calculated CYCLE-TIME 

When AUTOTUNE is completed, enter program (

 

) and select 

CYC.t 

in 

Level 1

. The display will read 

CYC.t:20 

(factory setting) 

To view the new calculated optimum value, press and hold both 

 

 

and 

 

buttons until indexing stops. The calculated value will be 

displayed eg. 

A16

. If acceptable, exit program (

 

) to implement this setting. 

 
To Pre-select Automatic Acceptance of AUTOTUNE Calculated CYCLE-TIME 

Before AUTOTUNE is initiated select 

CYC.t 

in 

Level1

, press and hold both 

 

 

and 

 

buttons until indexing stops at 

– –

. Exit 

program (

 

) to accept calculated value automatically. 

 
To Manually Pre-select Preferred CYCLE-TIME 

Before AUTOTUNE is initiated select 

CYC.t 

in 

Level 1

, press and hold both 

 

 

and 

 

or 

 

buttons until indexing stops at 

preferred value then exit program (

 

) to accept.

 

 

CYCLE-TIME RECOMMENDATIONS 

Output device 

Factory setting 

Recommended minimum

Internal relay : rLY / rLY1 / rLY2 

20 seconds 

10 seconds 

Solid state drives : SSd / SSd1 / SSd2 

20 seconds 

0.1 seconds 

 

PROGRAMMER - 

RAMP-SOAK

 

This feature enables the controller to ramp up or down from current temperature to a target setpoint at a pre-determined rate. It then 
controls at the target setpoint for an adjustable soak period before switching off the SP1 output. 
 

 Set 

Setpoint ramp rate (

0 to 9995 deg/hour) 

 From 

SPrr 

in Level 1, press and hold 

 

and 

 

or 

 

to scroll to required ramp rate. 

 Set 

Soak 

(if required) 0 to 1440 minutes 

 From 

SoAk 

– – in Level 1, press and hold 

 

and 

 

or 

 

to scroll to required Soak time. 

 Set 

Ramp on 

(Off: On: Hold) 

 From 

Sprn 

in Level 1, press and hold 

 

 

, then 

press 

 

to select 

On 

  Exit program (

 

) to enter settings into 

memory and commence ramp to target setpoint. 

 
Notes:  

In 

Ramp on 

configuration, if power is removed from the controller, the Ramp will re-start when power is restored. 

The 

Ramp hold 

option suspends the ramp at its last value. 

If no 

Soak 

period has been set, control at target setpoint continues indefinitely. 

SP2 deviation alarms follow the ramp setpoint and can be used to alarm “out of limits” ramp rate. 

 
WARNING: 

The Soak timer is triggered when the ramp setpoint reaches the target setpoint. If the ramp rate is set too fast for the 

process, the Soak timer will be triggered before the process temperature reaches the target setpoint.

 

S1 

F1 

F1 Fuse: 

1A time lag type to IEC127. CSA/UL rating 

250Vac 

S1 Switch: 

IEC/CSA/UL Approved disconnecting 

device

 