background image

Page 2 / 4 

 

Issue date: 25.02.2016

 

 

 

 

Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: 02778/6960-0 · fax: -400 · 

www.thermokon.com

· 

email@thermokon.de

 

SR65_DI_EasySens_Datasheet_en.docx   © 2016 

G

uidelines for Devices with Solar Energy Storage

 

Due  to  the  energy-

optimized  EnOcean  radio  technology  used  in  ”EasySens“  wireless  sensors,  the  devices  can  work  without 

batteries  and self-charge  themselves using  electric energy  generated  by integrated solar  cells.  This  makes the  devices  almost 
maintenance free and environmentally sound due to not having to replace batteries.  

For optimum use, the device should be mounted in a location with sufficient ambient brightness. Minimum illumination of 200 lx 
(artificial  light  or  ambient)  is  required  for  at  least  3  to  4  hours  each  day.  (The  health  and  safety  regulations  at  work  require  a 
minimum illumination of 500 lx for office workplaces).  

The solar cell should be mounted facing towards the window direction if possible. If the device has a temperature sensor, then 
even periodic direct sun radiation should be avoided due to incorrect false temperature readings. 

The mounting position should be selected so that the device will not be obstructed in the future: for example by placement areas, 
additional furniture or roll-fronted cupboards. 

The  sensor  is  supplied in  an operational  state.  If  the  sensor  has been  stored  in  darkness  for  longer periods,  the internal  solar 
energy storage will most likely need to be recharged. This would normally happen automatically during commissioning or during 
initial start up in ambient light. If the initial charge is not sufficient, the sensor will reach its full operating state up to 3 to 4 days, if 
the requirements for minimum illumination per day are met. The sensor will then transmit continuously in darkness as specified f 
(2/3 days on factory default telegram timing). Depending on the application it is also possible for the devices to operate in  darker 
rooms (with brightness <100 lx) by using the battery back-up option. Batteries to be used are listed in accessories. 

The operating time when using batteries will depend on the transmission frequency as well as the component aging and the self-
discharge of the battery. Standard operating time will be 5-10 years on factory default telegram timing. Changing of the device 
from solar to battery operation is done automatically by simply adding a battery to the device 

I

nformation about EasySens

®

 (radio) / airConfig general usage 

Basic information about EasySens

®

 radio and about general usage of our airConfig software, please download 

from the following link 
 

http://www.thermokon.de/ftp/info/Information_Radio_airConfig_en.pdf

 

T

echnical Data 

Radio technology 

EnOcean (IEC 14543-3-10) 

Frequency 

868 MHz 

Power supply: 

solar cell, internal super cap 
and battery LS14250 

Transmission interval 

configured via airConfig, default: Heartbeat cycle = 100 sec 

Inputs 

input for floating contact, contact resistance 

max.1000 Ω 

Connection electrical 

terminal block, max. 1,5 mm² 

Enclosure 

PA6.6, pure white with quick lock screws 

Protection 

IP65 according to EN60529 

Ambient condition 

-25..+65 °C, max. 85% rH, short term condensation 

Weight 

110 g 

Shipment 

1x battery LS14250 

O

verview of airConfig selectable radio telegrams 

A5-30-01

 

(standard) 

 

 

 

 

 

A5-30-02 

F6-02-xx, F6-03-xx 

F6-04-01 

D5-00-01 

A5-07-01 

A5-07-02 

EEP: 

The  structure  of  the  data  contained  in  the  telegram  can  be found  in  the  EEP  (EnOcean equipment  profile) list  provided  by  the 
EnOcean Alliance:  

http://www.enocean-alliance.org/eep/

. 

 

 

Reviews: