background image

INSTALLATION PROCEDURES

5

Completing the Installation . . .

1.  Begin final cable attachment by securing the end-of-circuit 

termination kit and working back toward the power supply.
•  Flexible heating cables are to be installed using attachment 

tape. Circumferential bands of tape should be installed at 
12” (30 cm) intervals to keep the cable in proper contact 
with the pipe. Refer to Table 2 below to calculate the num-
ber of rolls of attachment tape required based on the pipe 
diameter

 1

.

•  If applicable, refer to installation details provided with the 

project drawings or contact Thermon for additional infor-
mation regarding installation.

2.  In addition to the circumferential tape requirements,  a 

continuous covering of aluminum foil tape may be required 
when:
• Spray or foam urethane

2

 thermal insulation is applied.

• Heat tracing nonmetallic piping.
•  Design requirements dictate the use of aluminum tape to 

improve heat transfer.

3. Complete splice connections (if required) in accordance 

with the installation instructions provided with the splice kit.

4.  Install power connection kit in accordance to the detailed 

installation instructions provided with the kit.

5.  Before making power connections, repeat the megger test 

with at least a 500 Vdc megohmmeter (megger) between 
the heating cable bus wires and the heating cable metallic 
braid. IEEE 515.1 recommends that the test voltage for 
polymer insulated heating cables be 2500 Vdc. The mini-
mum acceptable level for the megger reading for any  
polymer-insulated heat tracing cable is 20 megohms.  
(Record 2 on Cable Testing Report) 

Heating Cable vs. Sensor Location

Temperature Control . . .

1.  When a line sensing controller is specified, the sensor should 

be placed at least 90° around the circumference from the 

heating cable, or at least 2" (5 cm) from the cable.  

Tape

Length

Pipe Diameter in Inches

½"-1"

1¼"

1½"

2"

3"

4"

6"

8"

10"

12"

14"

16"

18"

20"

24"

30"

36 yd

130'

115'

110'

95'

75'

65'

50'

40'

35'

30'

26'

23'

21'

19'

16'

13'

60 yd

215'

195'

180'

160'

125'

105'

80'

65'

55'

50'

43'

38'

35'

31'

27'

22'

Heating Cable 

(Typical)

Temperature  

Sensor

Table 2: Attachment Tape (Value Represents Approximate Linear Pipe Length Allowance Per Roll)

Ambient Sensing Thermostat

End Termination

Power Connection

L1

L2/N

Ambient Sensing Control Connection

Temperature Sensor

End Termination

Power Connection

L1

L2/N

Heating Cable

Pipewall Sensing Control Connection

Heating Cable

3.  When using an ambient sensing temperature controller, the 

mounting location should be representative of the coldest 

region, and the sensing element should not be exposed to 

direct sunlight or any additional heat source.

Notes . . .

1.  Table 2 assumes circumferential bands every 12” (30 cm) along the length of the piping.

2.  Verify exposure temperature of heating cable versus curing temperature of insulation.

2.  For pipewall sensing thermostatic control, the heating circuit 

is to be connected in series with the control contacts as 

shown in illustration below. The pipewall sensing thermostat 

may require more than one support point.

90°

Optional Third 

Heating Cable

Optional Second

Heating Cable

Summary of Contents for FLX Self-Regulating

Page 1: ...FLXTM Self Regulating Winterization Freeze Protection INSTALLATION PROCEDURES ...

Page 2: ... Remove dirt rust and scale with a wire brush and oil and grease films with a suitable solvent Refer to the FLX Cable Testing Report for required recording of test data and circuit information Upon Receiving Cable 1 Uponreceivingheatingcable checktomakesuretheproper type and output have been received All cables are printed ontheouterjacketwithpartnumber voltageratingandwatt output 2 Visually inspe...

Page 3: ... and for any splice loca tions Refer to illustration below for temporary installation Installation on Fittings and Equipment 1 Install heating cable in accordance with illustrations below Secure heating cable to piping using attachment tape 2 Elbows Locate the cable on the outside radius of an elbow to provide sufficient heat to compensate for the added pip ing material Secure the cable to the pip...

Page 4: ...le Attachment Tape Typical Pipe Size Valve Type Screwed Flanged Welded Pump Type Screwed Flanged 6 1 0 1 2 9 1 6 0 1 6 3 1 1 2 1 2 4 1 1 6 2 1 3 4 6 1 1 6 2 6 1 6 3 5 2 2 2 6 2 4 5 6 3 2 6 3 6 2 6 5 7 4 4 5 3 8 10 6 7 8 3 6 14 16 8 9 6 11 4 19 22 10 12 6 14 4 25 28 12 15 16 6 5 30 33 14 18 19 6 5 6 36 39 16 21 6 23 6 43 46 18 25 6 27 6 6 51 54 20 28 6 30 7 57 60 24 34 36 8 68 72 30 40 42 10 80 84 ...

Page 5: ...dc The mini mum acceptable level for the megger reading for any polymer insulated heat tracing cable is 20 megohms Record 2 on Cable Testing Report Heating Cable vs Sensor Location Temperature Control 1 Whenalinesensingcontrollerisspecified thesensorshould be placed at least 90 around the circumference from the heating cable or at least 2 5 cm from the cable Tape Length Pipe Diameter in Inches 1 1...

Page 6: ...n cannot be overemphasized Without insulation heat losses are generally too high to be offset by a conven tional heat tracing system 2 In addition to piping and in line equipment such as pumps and valves all heat sinks must be properly insulated This includes pipe supports hangers flanges and in most cases valve bonnets 3 Regardless of the type or thickness of insulation used a protective barrier ...

Page 7: ...al damage between the braid and the heating element small cuts or scuffmarks on the outer jacket will not affect the megger reading unless there was actual penetration through the braid and dielectric insulation jacket 4 Once the installation is complete but prior to installation of thermal insulation recheck the heating cable with at least a 500 Vdc megohmmeter megger between the heating cable bu...

Page 8: ...Date Witnessed By Date Record 2 After Installation Insulation Resistance M Ohms Tested By Date Witnessed By Date Record 3 After Thermal Insulation is Installed Insulation Resistance M Ohms Tested By Date Witnessed By Date Record 4 Final Commissioning Panel Number Breaker Number Volts Ambient Temperature deg F Recorded Amps Tested By Date Witnessed By Date FLX Cable Testing Report ...

Page 9: ... 396 5801 Facsimile 512 396 3627 800 820 HEAT www thermon com In Canada call 800 563 8461 Other Products Thermonoffersadditionalcut to lengthcablesor complete turn key systems for the following applications Hot Water Temperature Maintenance Freezer Floor Frost Heave Prevention Tank and Hopper Heating Instrument Tubing Bundles Control and Monitoring Systems ...

Reviews: