background image

MAN-IRD-012-05-E

 

 
 

 

 

 

6) Air filters - 

Must be replaced at least every two months. 

 
NOTES: 
1. 

Warranty  will  be  void  if  units  operate  under  low 

airflow conditions due to blocked filters. 
 

2

. Unit must not be operated without filters. 

 

REFRIGERANT CHARGE

 

These  units  are  not  standard  packaged  air 
conditioners.  They  are  specially  engineered 
refrigeration  products. 

Only  qualified  service 

personnel  should  start  and  service  these 
machines.  They  can  operate  as  low  as  70  psig 
(483 kPa) head pressure. The refrigerant charge of 
R404A is marked on the nameplate. Do not exceed 
the refrigerant charge marked thereon. 

 

DEFROST SYSTEM 

Field adjustment is provided for a selective defrosting 
frequency at 30 - 45 - 90 minute intervals. Also the 
defrost  temperature  termination  is  adjustable 

from 

55°F  to  70°F  (13°C  to  21°C)

.  In  effect, the defrost 

system is engineered  to work on a 

time initiated - 

temperature terminated principle

 with a frequency 

and termination adjustment range, if required. 
 
Initiation  of  the  defrost  cycle  can  only  occur  if  the 
suction  temperature  is  below  the  fixed  initiation 
temperature of 26°F (-3°C) for more then the defrost 
timer  setting  (30-45-90  min.).  If  the  suction 
temperature is above 26°F (-3°C) during the first sixty 
seconds  then  the  cycle  is  skipped.  If  the  suction 
temperature is 26°F (-3°C) or lower at any time during 
the  first  sixty  seconds,  then  the  defrost  cycle  will 
occur, timer will start counting at the end of the defrost 
timer setting (30-45-90 min.) the defrost cycle will be 
initiate. 
 
The  defrost  will  end  when  the  suction  temperature 
reaches 55°F (13°C) or higher depending on the field 
adjustments made afterwards. If the suction cannot 
reach the desired preset temperature due to excess 
ice or malfunction, a time safe termination will occur 

after 10 minutes.

 

 

POSSIBLE MALFUNCTION 

1) 

Low refrigerant charge 

2) 

High refrigerant charge 

3) 

Defective hot gas valve 

4) 

Defective de-ice control 

Refer to piping diagram for gas flow. (

Fig. 5

 
The installation of one or even two IRD Series units 

may not be sufficient to eliminate stagnation, 
especially when the ceiling structure creates 
obstacles for good air distribution. A minimum of 
two IRD Series units MUST be used in ice rink 
applications. 
 

IMPORTANT!!! 

It is of utmost importance that NO air is blown 
directly onto the ice surface since this causes 
the ice to melt. The units must be equipped with 
a 36 inch (0.9 m) discharge duct extension 
complete with adjustable horizontal and vertical 
louvers in the discharge grill. 
 
Units must be installed as shown in the drawing 
on the following page paying particular 
attention to the mounting height above the ice 
surface, and allowing a minimum of four feet 
between the inlet and any obstacles such as an 
end wall. This configuration is necessary in 
order to "scoop" out the moist air from the ice 
surface, without causing the ice to melt. 
 
IMPORTANT!!! 

Provide service access to the unit for maintenance, 
inspection and service of components. Minimum 
access area on all sides is 24 inches (0.6 m). A step 
ladder is not considered a safe means of access. 
Provide clearances according to the local building 
and electrical codes. 
 

Step 1 
Pre-installation Inspection

 

Remove packing material and inspect for internal 
and external shipping damage. 
In case of transport damage, notify the carrier as 
per instructions posted on the shipping crate. 
 

Step 2 
Location of the IRD Series Units 

(See also drawing fig 1 and  3) 
Provide service access to the unit for maintenance, 
inspection and service of components. Filters must 
be changed, the belt tension adjusted and the drain 
pan may require periodic cleaning. A step ladder is 
not considered a means of service access. 
Minimum service access clearance on all sides is 
two feet. 
 
DO NOT install the unit over the ice surface, as 
servicing will be dangerous. 
Units must be level to ensure proper draining of the 
condensate. 

Summary of Contents for IRD R404A Series

Page 1: ...om the ice surface then the horizontal duct louvers by others must be adjusted to direct the airflow away from the ice surface It is mandatory that this unit have a 36 inch 0 9 m discharge duct comple...

Page 2: ...refrigerant charge 3 Defective hot gas valve 4 Defective de ice control Refer to piping diagram for gas flow Fig 5 The installation of one or even two IRD Series units may not be sufficient to elimin...

Page 3: ...its can use the same switch Step 5 Discharge Duct Extension Provide a 36 inch 0 9 m discharge duct extension complete with horizontally and vertically adjustable louvers IMPORTANT Before starting up t...

Page 4: ...y during the active period or whenever high humidity is a problem When the return air temperature is low the IRD Series actually freezes moisture out of the air The coils have been designed for frost...

Page 5: ...ation at air inlet Follow duct design standards Unit undersized Recheck load calculations High head pressure Do not operate unit above 80 F 27 C Low airflow adjust blower belts Restricted filter dryer...

Page 6: ...Direct the airflow along the boards do not direct air over the ice surface 2 Discharge duct equipped with horizontally and vertically adjustable louvers supplied by others 3 Minimum horizontal distanc...

Page 7: ...ICE RINK DEFOGGER ELECTRICAL DIAGRAM Fig 4...

Page 8: ...MAN IRD 012 05 E 8 PIPING DIAGRAM Fig 5...

Page 9: ...ns checked for tightness Air flow and blower speed adjusted Units level and vibration isolated Drain connection tested and P trap filled Air entering temperature ____ F Minimum 4 feet Clearance on ret...

Reviews: