background image

MAN-IRD-012-05-E

 

 
 

 

 

 

 
 

Step 16

 

Check that the blower has correct rotation on three 
phase units. If not, then switch two of the three legs 
and try again. 
 

Step 17 

Check blower motor amperage. Check compressor 
amperage. Reading must not exceed that indicated 
on nameplate. 
 

Step 18 

Check compressor discharge line temperature. If 
above 200°F (93°C) and if the sight glass is full, 
adjust expansion valve to maintain 50-70°F (10-
21°C) above condensing temperature. If the sight 
glass is empty or bubbling, then refrigerant has 
been lost. Look for the leak, repair and recharge 
system until sight glass is full. Do not overcharge. 
 

Step 19 

Adjust louvers in discharge duct so that air is 
directly along the boards. DO NOT DIRECT OVER 
THE ICE SURFACE! 
 

Step 20 

Fill in the start-up report and warranty registration 
form, and forward a copy to sales agent, or 

Thermoplus air

 factory. 

Warranty is not valid until start-up report received at 
the factory. 
Leave the owner's manual complete with start-up 
report with the IRD unit. 
The IRD Series is remotely started by the remote 
on/off switch. Turn on the IRD units approximately 
one to two hours before the ice rink is to be used, 
and leave the units running continuously during the 

active period or whenever high humidity is a 
problem.  
When the return air temperature is low, the IRD 
Series actually freezes moisture out of the air. The 
coils have been designed for frost build-up. An 
automatic built-in defrost cycle engages periodically 
to eliminate the ice build-up. When a defrost cycle is 
initiated, the blower is shut off. The compressor 
continues to run during the defrost cycle. Once the 
defrost cycle is completed, the compressor stays in 
operation and the blower restarts. 
The IRD Series units are protected by an internal 
temperature limiting thermostat which is factory set 
at 30°F (-1°C). The IRD Series technology is so far 
advanced that it requires virtually no maintenance. 
 

Air Filters 

The air filters should be checked once per month. 
Dirty filters should be changed immediately and 
replaced with identical filters, which should be 
available locally. Clogged and dirty filters will 
seriously hamper the performance of the 
equipment. 
 

Blower Belt 

The following procedure should only be performed 
by a factory trained service technician. 

 

Check the belt for signs of wear and replace if 
severely worn or cracked. 
 

IMPORTANT! 
The IRD Series units must be fine-tuned on 
start-up for maximum energy efficiency and 
moisture removal capacity. Adjust the 
expansion valve for proper operation, a 8 to 
12°F (-13 to -11°C) superheat is recommended 
for optimal performance. 

 

Summary of Contents for IRD R404A Series

Page 1: ...om the ice surface then the horizontal duct louvers by others must be adjusted to direct the airflow away from the ice surface It is mandatory that this unit have a 36 inch 0 9 m discharge duct comple...

Page 2: ...refrigerant charge 3 Defective hot gas valve 4 Defective de ice control Refer to piping diagram for gas flow Fig 5 The installation of one or even two IRD Series units may not be sufficient to elimin...

Page 3: ...its can use the same switch Step 5 Discharge Duct Extension Provide a 36 inch 0 9 m discharge duct extension complete with horizontally and vertically adjustable louvers IMPORTANT Before starting up t...

Page 4: ...y during the active period or whenever high humidity is a problem When the return air temperature is low the IRD Series actually freezes moisture out of the air The coils have been designed for frost...

Page 5: ...ation at air inlet Follow duct design standards Unit undersized Recheck load calculations High head pressure Do not operate unit above 80 F 27 C Low airflow adjust blower belts Restricted filter dryer...

Page 6: ...Direct the airflow along the boards do not direct air over the ice surface 2 Discharge duct equipped with horizontally and vertically adjustable louvers supplied by others 3 Minimum horizontal distanc...

Page 7: ...ICE RINK DEFOGGER ELECTRICAL DIAGRAM Fig 4...

Page 8: ...MAN IRD 012 05 E 8 PIPING DIAGRAM Fig 5...

Page 9: ...ns checked for tightness Air flow and blower speed adjusted Units level and vibration isolated Drain connection tested and P trap filled Air entering temperature ____ F Minimum 4 feet Clearance on ret...

Reviews: