background image

 

 

ICE RINK DEFOGGER

 

If You Have a Problem…

 

Problem 

Suggested Causes and Solutions 

Dehumidifying coil iced-up 

With return air temperature below 64°F (18°C), this is normal. Unit 
should defrost automatically about every 30 - 45 - 90 minutes, as 
adjusted. 
Check operation of defrost timer and hot gas valve solenoid, replace if 
defective. 
Obstruction at air inlet. Allow 4 feet (1.2 m) minimum clearance 
between air inlet and nearest obstruction. 
Poor return air ductwork (if so equipped) creates stratification at air 
inlet. 
Ducts not recommend. 
Loose blower belt, adjust. 
Low refrigerant charge, add refrigerant. 
Dirty filters, replace. 
Wrong filter with too much air resistance, replace with disposable type. 
Return air too dry, set point to low (50% recommended). 

High Humidity 

Obstruction at air inlet. Allow 4 feet (1.2 m) minimum clearance 
between air inlet and nearest obstruction. 
Poor return air ductwork (if so equipped) creates stratification at air 
inlet. 
Follow duct design standards. 
Unit undersized. Recheck load calculations. 

High head pressure 

Do not operate unit above 80°F (27°C). 
Low airflow, adjust blower belts. 
Restricted filter dryers, replace. 
Manual shut off valve(s) not fully open, if so equipped. Open valves 
fully. 
Non-condensable gases in system. 

Low head pressure 

Do not operate unit below 30°F (-1°C) due to low limit thermostat 
adjustment. 
Low refrigerant charge, add refrigerant. 
Return air too dry, set point to low (50% recommended). 

Unit will not start 

This is normal if space above 80°F (27°C) or below 30°F (-1°C). 
Loose control or power wiring, tighten and check continuity. 
Anti-short cycle timer prevents start-up. 5 minutes maximum. 
Open thermal compressor protection, allow 1 hour for compressor to 
cool. 
Defective 240V control voltage transformer, replace. 
Defective fuse, replace. 
Check operation of defrost timer, replace if defective. 
Compressor "on" light not illuminated, unit off or no power supplied. 
Humidity is lower then set point (50% recommended). 

Unit noisy 

Verify crankcase heater. 
Blower ball bearing failure, replace. 
Loose belt or pulley, adjust. 

Summary of Contents for IRD R404A Series

Page 1: ...om the ice surface then the horizontal duct louvers by others must be adjusted to direct the airflow away from the ice surface It is mandatory that this unit have a 36 inch 0 9 m discharge duct comple...

Page 2: ...refrigerant charge 3 Defective hot gas valve 4 Defective de ice control Refer to piping diagram for gas flow Fig 5 The installation of one or even two IRD Series units may not be sufficient to elimin...

Page 3: ...its can use the same switch Step 5 Discharge Duct Extension Provide a 36 inch 0 9 m discharge duct extension complete with horizontally and vertically adjustable louvers IMPORTANT Before starting up t...

Page 4: ...y during the active period or whenever high humidity is a problem When the return air temperature is low the IRD Series actually freezes moisture out of the air The coils have been designed for frost...

Page 5: ...ation at air inlet Follow duct design standards Unit undersized Recheck load calculations High head pressure Do not operate unit above 80 F 27 C Low airflow adjust blower belts Restricted filter dryer...

Page 6: ...Direct the airflow along the boards do not direct air over the ice surface 2 Discharge duct equipped with horizontally and vertically adjustable louvers supplied by others 3 Minimum horizontal distanc...

Page 7: ...ICE RINK DEFOGGER ELECTRICAL DIAGRAM Fig 4...

Page 8: ...MAN IRD 012 05 E 8 PIPING DIAGRAM Fig 5...

Page 9: ...ns checked for tightness Air flow and blower speed adjusted Units level and vibration isolated Drain connection tested and P trap filled Air entering temperature ____ F Minimum 4 feet Clearance on ret...

Reviews: