pg. XXXII
All the sections of the smoke discharge tubes and the flue outlet must be easy to inspect and
remove for internal cleaning. CAUTION: if the flue outlet is not sufficiently insulated and /or if it is
too long it could generate condensation. It is advisable to provide a condensation drain near the
smoke outlet of the appliance. The appliance must always and only be installed in a single flue
outlet system dedicated exclusively to the appliance. If the appliance is connected to a flue
system that is non-compliant with the standards the appliance could show signs of
early damage due to an anomalous continual overheating of the heater itself : in
this case the damaged parts will not be replaced under warranty.
IF THE CHIMNEY CATCHES FIRE DO NOT HESITATE TO CALL THE FIRE
BRIGADE IMMEDIATELY.
K E Y
Inspection
Slope 3-5%
2-3 m MAX
Height more than 4 m.
Internal
External
Rain protection
Cover slab
Watertight steel sheet
9 ALARMS
9 ALARMS
9 ALARMS
9 ALARMS
9 ALARMS
The heater / boiler is programmed to communicate 4 fundamental alarms.
The alarms are listed below:
Pellets finished clean the burner
: is communicated when the temperature during the RUNNING mode drops below 42 °C. This
indicates that the appliance is switching off due to lack of pellets.
Start up failed clean the burner
: is communicated if after the start up phase the temperature does not rise above 42°C.
P GAS
: this occurs when the smoke outlet is partially blocked.
P H2O
: the pressure in the boiler has dropped below 0.3 bar.
To reset the alarm the fire must be out, disconnect the electric power supply, wait 2 seconds and power up the generator once again.