Page 31
Installation, use and maintenance guide
It must be possible to inspect and remove all the smoke tube sections for clean-out purposes.
CAUTION: if the flue outlet is not sufficiently insulated and /or if it is too long it could generate condensation. It is
mandatory to provide a condensation drain near the smoke outlet of the appliance. The appliance must always and only be
installed in a single flue outlet system dedicated exclusively to the appliance.
If the generator is connected to a non-compliant flue system the appliance could rapidly deteriorate due to an abnormal,
continuous overheating: in this case the damaged parts will not be covered by warranty.
IF THE CHIMNEY CATCHES FIRE DO NOT HESITATE TO CALL THE FIRE BRIGADE IMMEDIATELY.
10 – ALARMS
The appliance is programmed to communicate 7 fundamental alarms. The alarms are listed below:
AL PE: is communicated when the temperature during the WORK mode drops below the fixed threshold:
this indicates that the appliance is switching off due to lack of pellets. To reset the alarm simply press the flame button (1):
The appliance will begin a new start up phase. It is mandatory to empty and clean the brazier, and then to fill the pellet
tank before repeating the START phase.
AL AC: appears once the START phase has finished if the smoke does not reach the correct temperature. To reset the alarm
simply press the flame button (1):the appliance will begin a new start up phase. It is mandatory to empty and clean the
brazier before repeating the START phase: pellets emptied from the brazier must not be fed into the tank.
AL OP: this occurs when the smoke outlet is partially blocked. To reset the alarm the power to the appliance must be switched off
then on by turning the switch 0-1 at the back of the appliance.
Before restarting the appliance check for any irregularities such as blocked flue outlet, open firebox door... and solve the
problem.
AL T max: appears when the temperature of the appliance body exceeds 125°C. Once the causes for the overtemper ature have
been identified and remedied unscrew the plastic cover from the thermostat located at the back of the appliance and press
the button (the temperature of the appliance must cool down). To reset the alarm the power to the appliance must be
switched off then on by turning the switch 0-1 at the back of the generator.
AL SMOKE TEMP SENSOR: appears when the smoke thermocouple is damaged or absent.
AL SMOKE FAN : activates when the smoke suction unit sensor detects a very slow rotation speed:
clean the vent A3 , the smoke channels and the flue outlet (see para. 8). If the problem persists contact the
technical assistance service.
AL SMOKE RPM SENSOR : trips when the smoke suction unit revolution sensor fails to detect any rotation; the smoke suction unit
is not working, call the technical assistance.
To reset the alarms the power to the appliance must be switched off then on by turning the switch 0-1 at the back of the generator.