7.2.2.  FAQ. General indications.

Problem

Possible cause

Solution

The equipment doesn't start up when pressing 

over the corresponding key.

Internal fuse blown.

Consult with the S.T.S..

The equipment is ON but the loads do not 

have power supply

Jumpers at the output are not connected 
properly.

Connect the output jumpers.

There is no voltage in the outlets.

Check LS1 and LS2 (not available in models up to 1 kVA), are selected 
from "001" to "000".

Back up time is too short.

Battery is low or the load level is very low.

Recharge the battery for 24 hours as minimum.

Battery is depleted or damaged

Consult with the S.T.S. to replace it.

Continuous alarm and LCD in red colour.

Equipment fault

Consult with the S.T.S..

Buttons or keys are not operative.

Setting mode is not the suitable.

Checl the setting procedure.

Buttons or keys are faulty.

Consult with the S.T.S..

Tabla 12. 

Troubleshooting guide. Warning indications.

7.3. Warranty 

conditions.

The limited warranty only applies to those products that you ac-
quire for commercial or industrial use in the normal development 
of your business .

7.3.1. Covered 

product.

SPS.ADVANCE RT.

7.3.2. Warranty 

terms.

This product is guaranteed against any parts and/or labour de-
fect  for  12  months  period  from  its  commissioning  by  our  com-
pany staff or other specifically authorised, or 18 months from its 
factory delivery, whichever expires first. In case of failure of the 
product inside the warranty period, we must repair, at our facili-
ties at no cost, the faulty part or parts. The transport expenses 
and packaging will be borne to the user.

We guarantees for period time higher than 10 years, the avail-
ability of parts and spare parts, as hardware as software, as 
well as a complete assistance regarding the reparations, com-
ponents replacement and software updating.

7.3.3.  Out of scope of supply.

Our company is not forced by the warranty if it appreciates 
that the defect in the product doesn’t exist or it was caused by 
a wrong use, negligence, installation and/or inadequate testing, 
tentative of repairing or not authorized modification, or any other 
cause beyond the foreseen use, or by accident, fire, lightnings or 
other dangers. Neither it will cover, in any case, compensations 
for damages or injuries.

7.4. 

Description of the available 
maintenance and service 
contracts.

When  the  warranty  is  expired,  and  adapting  to  the  customer’s 
needs, has several maintenance modalities:

Preventive.

It guarantees a higher safety to preserve the correct operating of 
the equipments with a yearly preventive visit, in which the spe-
cialised technicians of our company make several tests and sets 
in the systems:

Ŗ

Measurement and write down input currents and voltages 

among the phases.

Ŗ

Measurement and write down output currents and voltages 

among the phases.

Ŗ

Measurement and write down floating currents and voltages 

, discharging and charging batteries.

Ŗ

Checking the logged alarms.

Ŗ

Checking and testing the measurements of the digital LCD 

panel:

 

ˆ

Input voltages

 

ˆ

Input currents

 

ˆ

Output voltages

 

ˆ

Output currents

 

ˆ

Temperatures

 

ˆ

Battery voltage and currents.

Ŗ

Check the battery status.

Ŗ

Check the fan status.

Ŗ

Bypass test.

Ŗ

Make a general cleaning of the equipment.

Ŗ

Controlling the mechanical parts and temperatures.

This way, it is guaranteed the perfect operating and the possible 
coming faults are avoided. 

These supervisions are usually done without shutdown the 
equipment. In those cases that a shutdown were needed, date 
and time would agree with the customer to do the task.

This maintenance modality covers, inside the working timetable, 
all the journey expenses and manpower.

Corrective.

When a fault occurs in the equipment operating, and previous 
notice to our Service and Technical Support (S.T.S.), in which a 
specialized technician will establish the failure scope and he will 
determine a first diagnostic, the corrective action starts. 

USER MANUAL

Thiele KG • V

orderer W

einberg 26 • D-71522 Backnang • T

el.:(07191)3560-0 • Fax.:(07191)3560-19 • info@thiele-electroni

c.de • www

.thiele-electronic.de

Thiele KG • V

orderer W

einberg 26 • D-71522 Backnang • T

el.:(07191)3560-0 • Fax.:(07191)3560-19 • info@thiele-electroni

c.de • www

.thiele-electronic.de

Vorderer Weinberg 26

 • D-71522 Backnang • 

Tel.:+49 (0)7191 3560-0 (Fax.:-19)

Summary of Contents for SPS.1000.ADV RT

Page 1: ...VANCE RT series UNINTERRUPTIBLE POWER SUPPLY USER S MANUAL Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 07191 3560 0 Fax 07191 3560 19 info thiele electronic de www thiele electronic de Thiele...

Page 2: ...x 07191 3560 19 info thiele electronic de www thiele electronic de Thiele KG Vorderer Weinberg 26 D 71522 Backnang Tel 07191 3560 0 Fax 07191 3560 19 info thiele electronic de www thiele electronic de...

Page 3: ...minals in UPSs 1kVA Emergency Power Off 4 3 6 Communication port 4 3 6 1 RS232 and USB interface 4 3 6 2 Smart slot 4 3 6 3 AS400 Interface with DB9 output option 4 3 6 4 Protection against transient...

Page 4: ...ntents the basic in structions and features for the equipment safety To not respect these indications can create material damages on the own equip ment installation or loads Notes of information symbo...

Page 5: ...ne of them It is essential that the cables that supplies the loads have the earth connection cable The protection earth must be connected to the frame or metallic chassis of any electrical equipment i...

Page 6: ...l conditions and avoid the possible condensations The UPS has to be completely dry before starting any instal lation task Do not store install or expose the equipment in corrosive wets dusty inflammab...

Page 7: ...ubber gloves and shoes Use tools with insulated handles Take off watches rings or other metal objects Do not place metal tools or objects over the batteries Never manipulate with your hands or through...

Page 8: ...safety requirements for UPS s used in ac cessible areas by end users EN IEC 60950 1 IT equipments Safety Part 1 General re quirements EN IEC 62040 2 Uninterruptible power supply UPS Part 2 EMC requir...

Page 9: ...with LCD Plastic beauty front Front view battery module for ADVANCE RT Fig 1 Front view models from 0 7 to 10 kVA and battery modules for extended back up times 3 1 2 Legend corresponding to the equip...

Page 10: ...ets LS2 Input connector for modem ADSL Fax line RS232 COM port Standard 3000 VA and B1 model IEC outlets LS1 USB COM port IEC inlet for AC power supply Earth connection for battery module Output conne...

Page 11: ...ule i Note relative to the batteries B0 and B1 acronyms stated the nomenclature related to batteries B0 The equipment is supplied without batteries and without accessories for them screws and electric...

Page 12: ...han 1000 VA it is possible to increase the standard back up time of the equipments by connecting additional modules and or to optimise the recharging time of the accumula tors by fitting chargers with...

Page 13: ...The available SNMP option for SPS ADVANCE RT series is a card to be inserted into the slot that the UPS has in its rear side The connection of the UPS with the SNMP is internal meanwhile the connecti...

Page 14: ...act has to be fitted in residual current device at the output of each transformer because due to its specification of isolation it will prevent the triggering of the protections fitted in the primary...

Page 15: ...s Cut the strips of cardboard enclosure Remove the accessories cables supports Remove the equipment or battery module from the pack aging keeping in mind that the it is needed the help of a second per...

Page 16: ...se way as its removing see section 4 2 4 1 4 2 4 3 Vertical assembling tower type Rotate the control panel according to section 4 2 4 2 Take the 4 plastic pieces A with angle shape supplied with the e...

Page 17: ...eak the needed trims to pass the connection bus Put the beautiful front cover back of the equipment and battery module as it is stated in section 4 2 4 1 4 2 4 5 19 rack cabinet assembling All models...

Page 18: ...of them is 2 units Proceed as follows Fix both adaptor angles A to the equipment and to the battery module as rack on their side by means of the supplied screws C B F G J K K H Fig 9 Model in rack mou...

Page 19: ...to the terminal before connecting the power supply to the input power block All the equipments have female IEC outlets in greater or lesser numbers depending on the power rate of the equipment Models...

Page 20: ...y of the two cables that goes from the button to the UPS were cut damaged On the other hand this failure would be immediately detected in the normally open EPO type with the inconvenience of the sudde...

Page 21: ...nPower is a UPS monitoring software which makes a user friendly interface of monitoring and management This software supplies an auto Shutdown for a system based on several PCs in case of an electrica...

Page 22: ...d that the equipment becomes blocked under the worst conditions It is better to not connect the loads of this kind due to the high quantity of energy resources that take from the UPS USER MANUAL Thiel...

Page 23: ...S start up with mains present For the daily start up of the equipment press over the start up key for more than 3 seconds the acoustic alarm will beep for 1 sec and the UPS will start up Fan will be s...

Page 24: ...Blue OPVH Fault Battery mode with output voltage too high Red OPVL Fault Output voltage is too low Red OPST Fault Short circuit at the output Red OVLD Warning Overload Red BATH Warning Battery voltage...

Page 25: ...e 001 Wide range 002 Gen set EBM External battery module 0 9 it is the quantity of battery modules TEST Auto test 000 Deactive 001 Active AR Automatic restart 000 Deactive 001 Active GF Green mode 000...

Page 26: ...e second to enter into the element to set 4 Select the configuration value Press the key to select the quantity of battery mod ules available for the UPS 5 Confirm the configuration Press the key for...

Page 27: ...he batteries so there are hazardous voltages in side Therefore before doing any reparation or maintenance task the internal battery fuses and or the interlink connections be tween them and the UPS hav...

Page 28: ...dequate testing tentative of repairing or not authorized modification or any other cause beyond the foreseen use or by accident fire lightnings or other dangers Neither it will cover in any case compe...

Page 29: ...al or total way with the purpose to be adapted to the customer s need Consult our Website to have more information 7 5 Technical service network Coverage both national and international from our Servi...

Page 30: ...Voltage accuracy battery mode 5 Voltage THD linear load 10 3 Voltage THD non linear load 12 6 Frequency With mains present synchronised to nominal of the input 45 55 55 65 Hz Free running battery mode...

Page 31: ...example the one supplied by the battery it is con tinuous any current that always maintain the polarity DSP It is the acronym of Digital Signal Processor A DSP is a system based on a processor or mic...

Page 32: ...irect cur rent This is done by rectifier diodes which can be solid state semiconductors vacuum or gassy valves as the mercury vapour Depending on the features of the alternating current power supply u...

Reviews: