3 Installation
Attention
The device must only be installed and wired by qualified skilled personnel.
The generally valid codes of practice and the respectively valid regulations
and standards are to be adhered to.
3.1 Recommendation for Site Selection
The device is designed for installation indoors. In the case of outdoor use, an additional
enclosure with an appropriate protection class is necessary.
Note
Please consider the temperature area of application and protection class when choosing the
site
3.2 Mechanical Installation
The Data logger is designed for snap-on installation onto a normal 35mm mounting rail (Hut-,
TS35). The mounting rail must be at least as long as the housing width (157mm, 9TE).
Sequence:
•
Install a 35mm mounting rail with a length of at least 9HP (157mm) at the installation
location.
•
Place the data logger DLU on the mounting rail that the top edge of the rail grips into
the corresponding groove of the data logger DLU.
•
Insert a screwdriver (blade width <4mm) into the slot of the clip and pull the clip
downward. The slot is located in the middle of the bottom edge of the housing.
•
Press the Data logger DLU completely onto the mounting rail.
•
Let go of the clip. The clip snaps in place behind the mounting rail.
•
Check whether the housing is firmly fitted onto the rail, by light shaking.