Installation
The inverter with a protection level of IP65 can be installed in the open air.
The inverter can not be installed under direction sunshine, or the internal
temperature of the inverter will be excessively high and thus the inverter
performance will be degraded for protecting the internal elements; or even
the temperature protection will be activated by the excessively high
temperature.
The inverter shall be installed in a cool & dry place with temperature from
-25
℃
- +60
℃
;The environmental relative humidity is not higher than 95%
and without any condensation.
The inverter LCD shall be leveled with eyes and with enough space in the
front for inspection.
To avoid of burning or electric shock, the inverter shall be installed beyond
reach of children. The temperature of some parts (e.g. : the heat radiator)
is high when the inverter is running.
Make sure the installation position does not shake.
The inverter shall be installed in a well ventilated place to ensure the
normal heat radiation.
The installation place shall be firm enough to support the inverter weight.
The inverter shall be installed on a vertical wall, or within 15°at most if
backwards to the wall.
Connecting terminal is located at the bottom.
Some parts ( e.g.: heat radiator) of the inverter runs with
a high temperature, so it is not suitable for installing near
inflammables or explosives.
When selecting an installation position, please avoid the influence
of noise and electromagnetic radiation to the environment.
The inverter can not be installed near any place of high external
electromagnetic radiation(e.g.: a TV tower, communication signal
tower or HV cables).
The inverter performance will be degraded if the environmental
temperature is 45
℃
above. Make sure the inverter is installed in a
well ventilated place so that the power generation can be
maximized.
MAX 15°