6.Circuit and checking
6.10
Checking the electromagnetic valve
Fault phenomenon 1
:
Leak
Detection method
:
Use soap water coating on the welding place of the
electromagnetic valve, pour the refrigerants into the system, to see if
having the bubble, If yes, meaning the electromagnetic valve itself has
the leakage.
Fault phenomenon 2
:
Not reversing
Detection method
:
With the hand to touch the electromagnetic valve, and
power on it ,the voltage is 187
-
220V, then to fell if the electromagnetic
valve has reversing action or hear if the electromagnetic valve has the
sound of reversing action, If yes, meaning the electromagnetic valve is
good.
Fault phenomenon 3
:
Reversing not reliable.
Detection method
:
After power on the electromagnetic valve , With the
hand to touch the electromagnetic valve, when fell the electromagnetic
valve already action, stop power on, , with the hand to touch the
electromagnetic valve should no longer have the reversing action feeling.
Electromagnetic valve fault the judgement of the process
Summary of Contents for HRF3603F
Page 1: ...Model HRF3603F Refrigerator Service Manual ...
Page 7: ...2 3 Evaporator structure 6 2 Appearance and structure Fuse Sensor Heater Evaporator ...
Page 10: ...9 4 Operation and functions 4 1 Display controls 4 Operation and functions ...
Page 11: ...10 4 Operation and functions 4 1 Display controls ...
Page 12: ...11 4 Operation and functions 4 1 Display controls ...
Page 15: ...14 4 4 Error display 4 Operation and functions 4 4 1 Error code ...
Page 21: ...20 5 Troubleshooting 5 1 Common problem and checking ...
Page 22: ...21 5 Troubleshooting ...
Page 54: ...53 7 Refrigeration system repair 7 2 Summary of repair ...
Page 55: ...54 7 3 Regualation for repair 7 Refrigeration system repair ...
Page 56: ...55 7 4 Practical work for repair 7 Refrigeration system repair ...
Page 57: ...56 7 4 Practical work for repair 7 Refrigeration system repair ...