background image

Installation and Commissioning

Instructions

Note: SENSALINK SENLP required for commissioning

Operational Notes

 

Temporary Override raises the light level of 

     linked by group but controlled by other devices.

all luminaires controlled directly by the panel and those 

 

Temporary Override dims the light level of 

     linked by group but controlled by other devices.

all luminaires controlled directly by the panel and those 

Setting and Recalling Scenes

Technical Data

Fascias must be ordered separately using the following part codes:

Scene Responses

To set a scene, select the required scene and adjust to the desired light level using the         buttons 
of the panel itself, or those of the SENSALINK SENLRC Infrared Remote Control, or the Utility functions of 
the SENSALINK SENLP. When the level is reached, it must be "learned" by the panel as the new value for 
that scene. This can only be done by sending the appropriate scene select signal continuously over a period 
of six seconds via the Infrared Remote Control link from a SENSALINK SENLRC or a SENSALINK SENLP.
With the device correctly aligned to the panel, press and hold the required scene select key until the luminaires 
under the direct control of the panel begin to flash on and off slowly. The LED of the scene button in question 
should flash during this process and be lit constantly at the end of this operation. 

To recall a pre-set scene simply press the appropriate button briefly. The LED of the button in question
should be lit at the end of this operation. This operation can also be carried out remotely using the
scene select buttons of the SENSALINK SENLRC.

When the temporary Override buttons have been used the LED of the latest scene selected will flash to 
indicate that the panel is no longer outputting a pre-set scene light level. The panel will remain in this state 
until it receives a new command from the Keypad, the SensaLink bus or an Infrared Remote Control device, 
or time-out occurs. 

Polished Brass: SENSALINK SENLSS V2 BR POL COVER (96237038)
Polished Chrome: SENSALINK SENLSS V2 CHR POL COVER (96237039)
Brushed Stainless Steel: SENSALINK SENLSS V2 RS BS COVER (96237040)
White: SENSALINK SENLSS V2 WHI COVER (96237041)

The ON button calls up the panel's programmed Entry Scene. The system may also be activated by a quick
press on any scene button, bringing that scene on. All luminaires directly controlled by the panel and those
linked by group but controlled by other devices will respond.

The OFF button switches off all luminaires controlled directly by the panel and those linked by zone but
controlled by other devices.

At the end of their useful life 
the packaging and product 
should be disposed of via a 
suitable recycling centre.
Do not dispose of with normal 
household waste.
Do not burn.

W4370B

Scene 1

The panel signals to detectors linked by group to enter Scene 1 regulating mode but will 

                     continue to output the previously commanded level to its directly controlled luminaires.

Scenes 2-6 The panel signals to detectors linked by group and its own output to enter the relevant scene
                     as previoulsy programmed.

2

SENSALINK BUS CABLE: 1.5mm  unscreened twisted pair

2

DIMMING CABLE: 1mm  2-core mains rated cable
DIMMING OUTPUT: up to 25 ballasts (either DSI or DALI - not mixed - to be configured via SENSALINK SENLP)
POWER SUPPLY:  230V

 ~

50Hz

POWER CONSUMPTION:  < 10W

2

TERMINAL CAPACITY:  2.5mm

o

ta  0 - 40 C
DIMENSIONS: Module (including supporting frame):  82mm x 144mm
                         Fascia: 86mm x 146mm

SENSALINK SENLSS V2 (96237037)

SensaLink Scene Switch Panel

Thorn Lighting Limited
www.thornlighting.com