KATflow 150
5 Commissioning
5.4.3
HART compatible output
The KF100 can also be configured with an optional module which responds to out-
put commands conforming to the HART protocol. Please refer to customer support
for further information.
HART® is a registered trademark of the HART Communication Foundation.
Wiring
Setup
Please refer to customer support.
Operation
Please refer to customer support.
5.4.4
Analogue current output 0/4 ... 20 mA
The analogue current outputs operate in a 4 ... 20 mA or 0 ... 20 mA span.
Current outputs may be assigned to process values in the “mode” section of the
output menu. The outputs can be programmed and scaled within the menu struc-
ture.
Wiring
Electrical
characterist-
ics
0/4...20 mA active and 4...20 mA passive options.
Galvanically isolated from main electronics and from other I/O's.
Passive: U=9...30 V, RLoad=50 ohm typical.
Resolution: 16 bit, accuracy: 0.1 % of MV.
Active: RLoad<500 ohm, U=30 V.
Resolution: 16 bit, accuracy: 0.1 % of MV.
5.4.5
Analogue voltage output 0 – 10 v
Voltage outputs may be assigned to process values in the “mode” section of the
output menu. The outputs can be programmed and scaled within the menu struc-
ture.
Wiring
Electrical
characterist-
ics
Galvanically isolated from main electronics and from other I/O's.
Range 0...10 V.
RLoad=1000 ohm.
Resolution: 16 bit, accuracy: 0.1% of MV.
35
Analogue outputs