17
Seat:
Verify the seat is level.
Verify the seat swivels 70° towards
each landing and locks into position.
Verify the lift will not operate when
the seat is not locked in the riding
position.
For optional folding seat: Verify the
seat will fold up and stay in the up
position.
Verify the seat belt works properly.
Clean Up:
Verify the lift is free of all grease,
dirt, etc.
V. E.T.L.
REQUIREMENTS
This E.T.L. listed stairway lift must meet the latest
ASME A18.1a specifi cations for the E.T.L. listing to
be valid.
The following rules must be complied to at the instal-
lation site.
Rule 7.1.1
A free passage width of no less than 20 in. shall be
provided. If the seat and platform can be folded when
not in use, the distance shall be measured from the
folded position.
Rule 7.1.2
The structure on which the equipment is installed shall
be capable of safely supporting the loads imposed.
Rule 7.1.3
The installation of all electrical equipment and wiring
shall conform to the requirements ANSI/NFPA 70.
Rule 7.6.4
At no point in its travel shall the edge of the footrest
facing the upper landing be more than 24 in. above
the step or landing as measured vertically.
Rule 7.7.2
No lift shall be installed to operate on a greater incline
than 45 deg. as measured on the mean.