TECHNICAL DATA
14
NA30 - Manual - 04 - 2022
Certifications
Reference standards
Product standard for measuring relays
EN 50263
CE Conformity
• EMC Directive
2014/30/EC
• Low Voltage Directive
2014/35/EC
Type tests
IEC 60255-6
3.2 INPUT CIRCUITS
Auxiliary power supply Uaux
Voltage
Nominal value (range)
24...48 V~/-
115...230 V~/110...220 V-
Operative range (each one of the above nominal values)
19...60 V~/-
85...265 V~/75...300 V-
Inrush current (max)
• 24 V-
6 A, 5 ms
• 48 V-
14 A, 5 ms
• 110 V-
20 A, 1 ms
• 230 V~
50 A, 1 ms
Frequency (for alternate voltage supply)
45...66 Hz
Max distortion factor ( for alternating voltage supply)
15%
Max alternating component (for dc voltage supply):
• Full wave rectified sine wave
100 %
• Sine wave
80 %
Power consumption:
• Maximum (energized relays, Ethernet TX)
10 W (20 VA)
• Maximum (energized relays, Ethernet FX)
15 W (25 VA)
Phase current input circuits
Relay nominal phase current
I
n
1 A or 5 A selectable by dip-switch
Permanent overload
25
A
Thermal overload (1 s)
500
A
Dynamic overload (half cycle)
1250 A
Rated consumption (for any phase)
≤
0.002 VA with
I
n
=1 A
≤
0.04 VA with
I
n
=5 A
Residual current input circuit
Relay nominal residual current
I
En
1 A or 5 A selectable by dip-switch
Permanent overload
25 A
Thermal overload (1 s)
500
A
Dynamic overload (half cycle)
1250 A
Rated consumption
≤
0.006 VA with
I
En
=1 A
≤
0.12 VA with
I
En
=5 A
Residual voltage input circuit
Relay residual nominal voltage
U
En
50...130 V
Permanent overload
130 V
Thermal overload (1 s)
200 V
Rated consumption
≤ 0.5 VA
Binary input circuits
Quantity 5
Type
optocoupler
Operative range 24...265
V~/-
Min activation voltage
U
DIGmin
18
V
Max consumption, energized
I
DIG
3
mA
Block input (Logic selectivity)
Quantity 1
Type
polarized wet input (powered by internal isolated supply)
Max consumption, energized
5 mA
3.3 OUTPUT CIRCUITS
Relays
Quantity 6
Type of contacts K1, K2
changeover (SPDT, type C)
Type of contacts K3, K4, K5
make (SPST-NO, type A)
Type of contacts K6
break (SPST-NC, type B)