APPENDIX
213
NA30 - Manual - 04 - 2022
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
IE>>> Logical block
IE>>>BLK1
OFF | ON
IE>>> Input selective block
IE>>>BLK2IN
OFF | ON
IE>>> Output selective block
IE>>>BLK2OUT
OFF | ON
IE>>> Internal selective block
IE>>>BLK4
OFF | OUT | IN
IE>>> Second harmonic restraint
IE>>>2ndh-REST
OFF | ON
IE>>> Breaker failure
IE>>>BF
OFF | ON
IE> Disabling by IE>>> start
IE>disbyIE>>>
OFF | ON
IE>> Disabling by IE>>> start
IE>>disbyIE>>>
OFF | ON
IE>>> Start relays
IE>>>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
IE>>> Trip relays
IE>>>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
IE>>> Start LEDs
IE>>>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
IE>>> Trip LEDs
IE>>>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Definite time
50N/51N Third threshold definite time
State
OFF | ON
Pickup value
IEn
0.002 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
IE>>>def within CLP
IECLP>>>def
IEn
0.002 ... 0.999 step = 0.001
1.00 ... 10.00 step = 0.01
IE>>>def Operating time
Value
s
0.03 ... 10.00 step = 0.01
Residual overvoltage - 59N
Common configuration
59N Operation from 74VT external
74VText59N
OFF | Block
UE> Element
Setpoints
UE> Enable
UE> Enable
OFF | ON
UE> Curve type
UE>Curve
INVERSE | DEFINITE
UE> Reset time delay
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE> Logical block
UE>BLK1
OFF | ON
UE> Breaker failure
UE>BF
OFF | ON
UE> Start relays
UE>ST-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE> Trip relays
UE>TR-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
UE> Start LEDs
UE>ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
UE> Trip LEDs
UE>TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Definite time
59N First threshold definite time
State
OFF | ON
Pickup value
UEn
0.01 ... 0.70 step = 0.01
UE>def Operating time
Value
s
0.07 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Inverse time
59N First threshold inverse time
State
OFF | ON
Pickup value
UEn
0.01 ... 0.50 step = 0.01
UE>inv Operating time
tUE>inv
s
0.10 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
UE>> Element
Setpoints
UE>> Reset time delay