APPENDIX
220
NA30 - Manual - 04 - 2022
ThAL6 Alarm LEDs
ThAL6-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Th>6 Trip
Th>6 Enable
Th>6 Enable
OFF | ON
26 PT6 Trip threshold
Th>6
^C
0 ... 200 step = 1
Th>6 Operating time
Value
s
0 ... 100 step = 1
Th>6 Breaker failure
Th>6BF
OFF | ON
Th>6 Trip relays
Th>6-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Th>6 Trip LEDs
Th>6-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
PT7 Probe
ThAL7 Alarm
ThAL7 Enable
ThAL7 Enable
OFF | ON
26 PT7 Alarm threshold
ThAL7
^C
0 ... 200 step = 1
ThAL7 Operating time
Value
s
0 ... 100 step = 1
ThAL7 Alarm relays
ThAL7-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
ThAL7 Alarm LEDs
ThAL7-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Th>7 Trip
Th>7 Enable
Th>7 Enable
OFF | ON
26 PT7 Trip threshold
Th>7
^C
0 ... 200 step = 1
Th>7 Operating time
Value
s
0 ... 100 step = 1
Th>7 Breaker failure
Th>7BF
OFF | ON
Th>7 Trip relays
Th>7-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Th>7 Trip LEDs
Th>7-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
PT8 Probe
ThAL8 Alarm
ThAL8 Enable
ThAL8 Enable
OFF | ON
26 PT8 Alarm threshold
ThAL8
^C
0 ... 200 step = 1
ThAL8 Operating time
Value
s
0 ... 100 step = 1
ThAL8 Alarm relays
ThAL8-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
ThAL8 Alarm LEDs
ThAL8-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Th>8 Trip
Th>8 Enable
Th>8 Enable
OFF | ON
26 PT8 Trip threshold
Th>8
^C
0 ... 200 step = 1
Th>8 Operating time
Value
s
0 ... 100 step = 1
Th>8 Breaker failure
Th>8BF
OFF | ON
Th>8 Trip relays
Th>8-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Th>8 Trip LEDs
Th>8-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Diagnostic
PT100 probe diagnostic relays
PT100Diag-K
K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
PT100 probe diagnostic LEDs
PT100Diag-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8 |
L9 | L10
Thermal image - 49
Common configuration
Initial thermal image
DthIN
DThetaB 0.0 ... 1.0 step = 0.1
Reduction factor at inrush
KINR
1.0 ... 3.0 step = 0.1
Thermal time constant
T
min
1 ... 200 step = 1
DthCLP Operating mode
DthCLP Mode
OFF | ON - Element blocking | ON - Change setting
DthCLP Activation time
Value
s
0.00 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1