SETTING AND COMMISSIONING
315
NVA100X-D - Manual - 02 - 2016
NVA100X-D _menuset3a.ai
PREVIOUS SET MENU’
PREVIOUS PROFILE A MENU’
PROCEED SET MENU’
SET
PROFILE A
PROCEED PROFILE A MENU’
50N(C)/51N(C) >>
50N.1/51N.1
87NHIZ.1 >>
IE1> Element
>>
IE1>> Enable
OFF
Type
IE1CLP>> Mode OFF
tE1CLP>> 0.10
s
tE1>>RES 0.00
s
IE1>>def OFF
1.00
IEn1
IE1CLP>>def
2.00IEn1
tE1>>def 1.00
s
IE1>>BLK1 OFF
IE1>>BLK2IN OFF
IE1>>BLK2OUT OFF
IE1>>BLK4 OFF
IE1>>2ndh-REST OFF
IE1>>BF OFF
IE1>disbyIE1>> OFF
Relays IE1>>
IE1>>ST-K -
IE1>>TR-K -
LEDs IE1>>
IE1>>ST-L -
IE1>>TR-L -
IE1> Enable
OFF
Type
Characteristic:
IE1>Curve DEFINITE
IE1CLP> Mode
OFF
tE1CLP> 0.10
s
tE1>RES 0.00
s
IE1>def OFF
1.00
IEn1
IE1CLP> def
2.00IEn1
tE1>def 1.00
s
IE1>inv OFF
1.00 In
IE1CLP>inv 2.00 In
tE1>inv 10.0
s
IE1>BLK1 OFF
IE1>BLK2IN OFF
IE>BLK2OUT OFF
IE1>BLK4 OFF
IE1>2ndh-REST OFF
IE1>BF OFF
Relays IE1>
IE1>ST-K -
IE1>TR-K -
LEDs IE1>
IE1>ST-L -
IE1>TR-L -
IE1>>> Enable OFF
IE1CLP>>> Mode OFF
tE1CLP>>> 0.10
s
tE1>>>RES 0.00
s
IE1>>>def OFF
1.00
IEn1
IE1CLP>>>def
2.00IEn1
tE1>>>def 1.00
s
IE1>>>BLK1 OFF
IE1>>>BLK2IN OFF
IE1>>>BLK2OUT OFF
IE1>>>BLK4 OFF
IE1>>>2ndh-REST
OFF
IE1>>>BF OFF
IE1>disbyIE1>>>
OFF
IE1>>disbyIE1>>>
OFF
Relays IE1>>>
IE1>>>ST-K -
IE1>>>TR-K -
LEDs IE1>>>
IE1>>>ST-L -
IE1>>>TR-L -
IE1>> Element
>>
IE1>>> Element
>>
50N.2/51N.2
87NHIZ.2 >>
IE2> Element
>>
IE2>> Enable
OFF
Type
IE2CLP>> Mode OFF
tE2CLP>> 0.10
s
tE2>>RES 0.00
s
IE2>>def OFF
1.00
IEn1
IE2CLP>>def
2.00IEn2
tE2>>def 1.00
s
.............
Relays IE2>>
IE2>>ST-K -
IE2>>TR-K -
LEDs IE2>>
IE2>>ST-L -
IE2>>TR-L -
IE2> Enable
OFF
Type
Characteristic:
IE2>Curve DEFINITE
IE2CLP> Mode
OFF
tE2CLP> 0.10
s
tE2>RES 0.00
s
IE2>def OFF
1.00
IEn2
IE21CLP>def
2.00IEn2
...............
Relays IE1>
IE2>ST-K -
IE2>TR-K -
LEDs IE2>
IE2>ST-L -
IE2>TR-L -
IE2>>> Enable OFF
IE2CLP>>> Mode OFF
tE2CLP>>> 0.10
s
tE2>>>RES 0.00
s
IE2>>>def OFF
1.00
IEn2
IE2CLP>>>def
2.00IEn2
tE2>>>def 1.00
s
..........
Relays IE1>>>
IE1>>>ST-K -
IE1>>>TR-K -
LEDs IE1>>>
IE1>>>ST-L -
IE1>>>TR-L -
IE2>> Element
>>
IE2>>> Element
>>
IEC> Element
>>
IEC>> Enable
OFF
Type
IECCLP>> Mode OFF
tECCLP>> 0.1
s
tEC>>RES 0
s
IEC>>def OFF
1 In
IECCLP>>def 2
In
tEC>>def 1
s
IEC>>BLK1 OFF
IEC>>BLK2IN OFF
IEC>>BLK2OUT OFF
IEC>>BLK4 OFF
IEC>>2ndh-REST OFF
IEC>>BF OFF
IEC>disbyIEC>> OFF
Relays IEC>>
IEC>>ST-K -
IEC>>TR-K -
LEDs IEC>>
IEC>>ST-L -
IEC>>TR-L -
IECType51NC IECL
IEC> Enable
OFF
Type
Characteristic:
IEC>Curve DEFINITE
IECCLP> Mode
OFF
tECCLP> 0.1
s
tEC>RES 0
s
IEC>def OFF
1 IEn
IECCLP>def 2
IEn
tEC>def 1
s
IEC>inv OFF
1 In
IECCLP>inv 2
In
tEC>inv 10
s
IEC>BLK1 OFF
IEC>BLK2IN OFF
IEC>BLK2OUT OFF
IEC>BLK4 OFF
IEC>2ndh-REST OFF
IEC>BF OFF
Relays IEC>
IEC>ST-K -
IEC>TR-K -
LEDs IEC>
IEC>ST-L -
IEC>TR-L -
IEC>>> Enable OFF
IECCLP>>> Mode OFF
tECCLP>>> 0.1
s
tEC>>>RES 0
s
IEC>>>def OFF
1 In
IECCLP>>>def 2
In
tEC>>>def 1
s
IEC>>>BLK1 OFF
IEC>>>BLK2IN OFF
IEC>>>BLK2OUT OFF
IEC>>>BLK4 OFF
IEC>>>2ndh-REST
OFF
IEC>>>BF OFF
IEC>disbyIE>>> OFF
IEC>>disbyIE>>>
OFF
Relays IEC>>>
IEC>>>ST-K -
IEC>>>TR-K -
LEDs IEC>>>
IEC>>>ST-L -
IEC>>>TR-L -
Common
>>
IEC>> Element
>>
IEC>>> Element
>>