INSTALLATION
299
NVA100X-D - Manual - 02 - 2016
6.4 RATED
I
N AND
I
EN SETTINGS
The values of the relay rated current can be set to 1 A or 5 A via ThySetter sw; parameters are avail-
able in the
Set \ Base
menu.
6.5 LED
COMMISSIONING
Following indicator LEDs are available on the front panel:
LED ON (green): if no diagnostic anomalies are detected, the green LED is turned ON while any
fault is highlighted by fl ashing.
LED START (yellow) committed for start information of any protective functions.
LED TRIP (red) committed for trip information of any protective functions LED 1...13 (red) are freely
assignable from the user to any protective and/or control functions.
6.6 FINAL
OPERATIONS
Before energizing the electric board, it is advisable to check that::
The auxiliary voltage in the panel falls within the operative range of Pro_NX relays.
The rated current (1 A or 5 A) of the line CT’s corresponds to the setting of Pro_NX relays.
All wirings are correct.
All screws are tightly screwed.
•
•
•
•
•
•
•