FUNCTION CHARACTERISTICS
147
If the CLP function (Cold Load Pick-up) is enabled for blocking 49, the thermal image is blocked for an
adjustable time interval, starting from the circuit breaker closure.
2
The operating mode parameter may be select by setting
ON-Element blocking
the
DThCLP Mode
parameter inside the
Set \ Profile A (or B) \ Thermal image-49LT \
Common configuration
menu.
If the CLP function (Cold Load Pick-up) is enabled for threshold change, the equivalent thermal
current may be decreased by means a
K
INR
factor for an adjustable time interval, starting from
the circuit breaker closure.
3
The operating mode parameter may be select by setting
ON-Chan-
ge setting
the
DThCLP Mode
parameter inside the
Set \ Profile A (or B) \ Thermal image-49LT \
Common configuration
menu.
The operating mode parameter may be select by setting
ON-Change setting
the
DThCLP Mode
parameter inside the
Set \ Profile A (or B) \ Thermal image-49LT \
Common configuration
menu.
La selezione del modo di funzionamento per la modifica della soglia è presente nel menù
Set \ Pa-
rametri configurazione A(o B) \ Immagine termica - 49LT \
Configurazioni comuni
programmando
ON-Modifica soglia
il parametro
DThCLP Mode
.
Second harmonic restraint
For the Dth> threshold, a block from the second harmonic restraint may be set by setting
ON
the
DTh>2ndh-REST
parameter inside the
Set \ Profile A (or B) \ Thermal image-49LT \
Common configuration
menu.
All elements can be enabled or disabled by setting
ON
or
OFF
the
DThetaAL1 Enable
,
DThe-
taAL2 Enable
and/or
DTheta> Enable
parameters inside the
Set \ Profile A (or B) \ Thermal
image-49LT \
DthAL1 Element
(
DthAL2 Element
,
Dth> Element)
menus
>
.
The trip element (Dth>) may be inhibited when a start of at least one of the overcurrent element
(50/51) is active, if the
Dth>disby50-51
parameter is set
ON
inside the
Set \ Profile A (or B) \Ther-
mal image-49LT \
Dth> Element
menu.
The D
q
IN
parameter sets a minimum level of previous thermal image D
q
p
when the protection relay
is powered or when a remote (binary input) or local (keyboard or Thyvisor) command is issued.
The
DthIN
parameter may be adjusted inside the
Set \ Profile A (or B) \ Thermal image-49LT \
Common configuration
menu.
To active the D
q
IN
preset value remotely, a binary input must be programmed as
Init DTheta
fun-
ction inside the
Set \ Board 1(2) inputs \ Binary input IN1-1...(IN1-x)
menus.
Breaker failure (BF)
Dth> threshold can be associated to BF (H) and BF (L) protection by activating the relative parameter
in the matrices “Selection of function tripping for BF (H)” or “Selection of function tripping for BF (L)”
all-F49LT.ai
General logic diagram of the thermal image elements - 49LT
K
INR
T
DthIN
DthCLP Mode
Dth2ndh REST
tDthCLP
Common configuration
I
th
Dth> Element
Trip DTh>
DTh>
Enable
DTh>
BLK4OUT
Dth>BLK4
Start I>
&
BLK2OUT
Dth>BLK2OUT
&
Trip Dth>
Trip Dth>
BLK2INDth>
Block2
&
Dth>BLK2IN
&
DthAL1 Element
DThAL1
DThAL1
DThAL1
DThAL1
Enable
I
th
BLK4OUT
DthAL1BLK4
&
BLK2OUT
DthAL1BLK2OUT
&
Trip Dth>
Block1
BLK1DthAL1
&
DthAL1BLK1
&
Dth>AL1
DthAL1
BLK2INDthAL1
Block2
&
DthAL1BLK2IN
&
DthAL2
BLK2INDthAL2
Block2
&
DthAL2BLK2IN
&
DthAL2 Element
DThAL2
DThAL2
DThAL2
Enable
I
th
BLK4OUT
DthAL2BLK4
&
BLK2OUT
DthAL2BLK2OUT
&
Block1
BLK1DthAL2
&
DthAL2BLK1
&
Dth>AL2
Dth>AL2
Dth>AL2
Block1
BLK1Dth>
&
Dth>BLK1
Trip Dth> &
&
50-51 inhibition
Dth>disby50-51
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021