234
FUNCTION CHARACTERISTICS
One alarm and one trip threshold are available.
The recomputed insulation resistance is compared with the setting values (
R
FAL<
,
R
F
<<); a start
is issued when the insulation resistance drops below an adjustable threshold; after expiry of the
associated operate time (
t
RFAL
<,
t
RF
<<) a trip command is issued; if instead the insulation resistance
overcomes the threshold, the element it is restored.
Each element can be enabled or disabled by setting
ON
or
OFF
the
State
parameter inside the
Profile A (or B) \ Rotor earth fault - 64F \ Alarm configuration, (Trip configuration) \ Setpoints
menu.
The alarm threshold (
R
FAL<
), may be inhibited by start of the second threshold (
R
F
<<) by setting
ON
the
Alarm threshold inhibition
parameter available inside the
Profile A (or B) \ Rotor earth fault -
64F \ Trip configuration \ Setpoints
menu.
La protezione è abilitata nel campo di frequenza 20...70 Hz (Blocco funzionale - Block3).
t-int-F64F.ai
R
F
R
F
<<
R
FAL
<
t
RF
<<
t
t
RFAL
<
TRIP
General operation time characteristic for the rotor earth fault elements - 64F
all-F64F.ai
R
F
R
F
ON=inhibit
2nd Pickup Element
1st Pickup Element
Block1
Block1
Block3
Block1
Block3
&
Block1
State
RFAL< inhibition
R
FAL
<
t
RFAL
<
State
R
F
<<
t
RF
<<
RFAL< inhibition
R
FAL
< Start
R
FAL
< Trip
R
<< Start
R
<< Start
R
<< Trip
Logic diagram concerning the rotor earh fault element - 64F
Fun-F64F_S1.ai
≥
1
U
F
< Inhibition
(ON
≡
Inhibit)
IF Start
=0 if 20≤f≤70 Hz
&
RESET
t
RFAL<
0
T
TR
IP
PI
NG M
AT
RI
X
(LE
D+R
EL
AY
S)
t
RFAL<
R
FAL
< Start
R
FAL
< Start
R
FAL
< Start
R
FAL
< Trip
R
FAL
< Trip
R
FAL
< Trip
F64FS1 Block3
R
FAL
< Block1
&
&
&
Enable (ON
≡
Enable)
Block1 input (ON
≡
Block)
Block1
Block1
Block1
R
F
R
F
≤
R
FAL
<
R
FAL
<
Binary input INx (x=1...8-16)
T
0
Logic
INx
t
ON
INx
t
ON
INx
t
OFF
T
0
n.o.
n.c.
INx
t
OFF
Logic diagram concerning the alarm threshold (RFAL<) of the rotor earth fault element - 64F
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021