50
TECHNICAL DATA
3.9
METERING
—
Accuracy
MEASURE
Reference values
Accuracy
Reference values
Accuracy
Phase current
0.1
I
n
0.2%
1
I
n
0.03%
Measured residual current
0.01
I
En
0.3%
1
I
En
0.02%
Calculated residual current
0.1...1
I
ECn
2%
1
I
ECn
0.3%
Phase voltage
0.1
U
n
0.2%
1
U
n
0.03%
Measured residual voltage
0.01
U
En
0.02%
0.1
U
En
0.02%
Calculated residual voltage
0.01
U
ECn
0.5%
0.1
U
ECn
0.3%
Power - Energy
0.01
P
n
2%
0.1...1 Pn
0.3%
Frequency
0.02
U
n
3 mHz
1
U
n
2 mHz
Phase
0.002
I
En
- 0.004
U
En
1.5°
0.005
I
En
- 0.01
U
En
- 0.1
I
En
- 0.5
U
En
0.2°
Positive/Negative sequence current
I
1
or
I
2
= 0.5
I
n
0.5%
I
1
or
I
2
= 0.5
I
n
0.5%
Positive/Negative sequence voltage
U
1
or
U
2
= 0.01
U
n
4%
U
1
or
U
2
= 0.15
U
n
0.3%
Pickup and operate time
1.5 x setting for fist element
5% ± 10 ms
2.5 x setting for other elements
5% ± 10 ms
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021