Synergy Controller Technical Manual, Revision H
Page 143
11.2 UUT Temperatures
The UUT Module (Unit-Under-Test) is a 16-channel thermocouple data acquisition unit. Developed to expand
the input capabilities of the Synergy Controller, the UUT module captures and logs data from the test. Up to
four modules can be attached to the Synergy Controller for a total of 64 thermocouple inputs. The UUT data
can optionally be logged and the log file may be used for analysis, graphing and reporting. The Synergy
Controller’s UUT window, shown below, displays the temperature readings from the UUT module.
UUT Temperatures
See
Section 13.0 UUT Module (Unit Under Test)
for a more detailed discussion of
the UUT module and its capabilities.
Browse to the
/Calibration/Input /UUT
folder in the
Setup screen to calibrate these inputs.
11.3 Digital Outputs
Digital Outputs
The Digital Outputs Screen displays the status of
the 32 Digital Outputs of the controller. LEDs
indicate the status of each output.
♦
Grey LED: Output Off (On/Off type)
♦
Red LED: Output On (On/Off type)
♦
Yellow LED: Time (Proportioning Type)
The information bar at the bottom indicates the
output designation and the status of the selected
output.
The Digital Outputs window displays the on/off/time proportioning states of the controller’s digital outputs.
These outputs control the chamber’s devices such as compressors and heaters. This screen also displays
the event states, alarm states and the percent heating and cooling requested from the heating and cooling
devices.
Additional information concerning each output is displayed in the text box at the bottom of the screen when
the output is selected. The text box displays the output designation numbers(s) and the status of the output.
Percentage output values between 101 and 199 indicate that an output is set to instantaneously mirror the
indicated output. For example, if an output’s time proportioning value is 112% then it is mirroring output 12.
Percentage outputs between 201 and 199 indicate that an output is the complement of the indicated output.
For example, if an output’s time proportioning value is 218% the output is instantaneously the opposite of
output 18.
Summary of Contents for Synergy Compact
Page 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Page 71: ...Synergy Controller Technical Manual Revision H Page 71...
Page 106: ...Synergy Controller Technical Manual Revision H Page 106...
Page 123: ...Synergy Controller Technical Manual Revision H Page 123...
Page 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Page 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Page 188: ...Synergy Controller Technical Manual Revision H Page 188...
Page 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Page 294: ...Synergy Controller Technical Manual Revision H Page 294...
Page 312: ...Synergy Controller Technical Manual Revision H Page 312...
Page 345: ...Synergy Controller Technical Manual Revision H Page 345...
Page 346: ...Synergy Controller Technical Manual Revision H Page 346...