Step 1. Wire the Granville Philips 10 Volt output thru a 2:1 voltage divider (1K/1K Ohm) as
shown below. Alternatively, Analog 2, 3 or 4 can be used. A precision 1% metal film resistor
suitable for this application is the Panasonic ERO-S2PHF1001 available from Digikey.
Signal
Olympic Board Connector-Pin
Reference
Analog Input 1 (See Note)
P2-1
P2-7
Analog Input 2
P2-5
P2-7
Analog Input 3
P2-6
P2-7
Analog Input 4
P2-11
P2-7
Note: High Resolution Analog 1 should always be connected to a sensor or shorted to Analog
Common otherwise the open sensor detection circuitry (present on Analog 1 only) will
negatively affect the accuracy of the other inputs.
Step 2. Select the appropriate chamber setup
from the Chamber Setup folder and reboot as
instructed. For example, the Temperature
Pressure selection is shown at left.
Summary of Contents for Synergy Compact
Page 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Page 71: ...Synergy Controller Technical Manual Revision H Page 71...
Page 106: ...Synergy Controller Technical Manual Revision H Page 106...
Page 123: ...Synergy Controller Technical Manual Revision H Page 123...
Page 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Page 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Page 188: ...Synergy Controller Technical Manual Revision H Page 188...
Page 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Page 294: ...Synergy Controller Technical Manual Revision H Page 294...
Page 312: ...Synergy Controller Technical Manual Revision H Page 312...
Page 345: ...Synergy Controller Technical Manual Revision H Page 345...
Page 346: ...Synergy Controller Technical Manual Revision H Page 346...