Low Artificial Load
This output energizes the Artificial Loading bypass solenoid to provide refrigerant flow to the compressor
when operating with temperature control only.
Output is Time Proportioning the inverse of the PID Cool output
Control Parameters
Default Value:
Range:
Channel 1 Proportional Band Cooling
5
0 - 50 Degrees C
Reset for Channel 1 Cooling
0.07
0 - 9.9 Repeats/minute
Rate for Channel 1 Cooling
0
0 - 9.9 Minutes
Cycle Time for Channel 1 Cooling
7
1 - 60 Seconds
Rate Band for Channel 1 Cooling
0
0 - 7 Seconds
High Artificial Load
Output is On/Off
Control Parameters
Default Value:
Range:
Compressor Cut In Logic (Input 3)
When closed, selects Compressor Cut In Logic. Uses a
pressure switch
There is a one-minute turn on timer that is reset while the compressor is off.
Output mirrors the High Stage Compressor
Summary of Contents for Synergy Compact
Page 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Page 71: ...Synergy Controller Technical Manual Revision H Page 71...
Page 106: ...Synergy Controller Technical Manual Revision H Page 106...
Page 123: ...Synergy Controller Technical Manual Revision H Page 123...
Page 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Page 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Page 188: ...Synergy Controller Technical Manual Revision H Page 188...
Page 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Page 294: ...Synergy Controller Technical Manual Revision H Page 294...
Page 312: ...Synergy Controller Technical Manual Revision H Page 312...
Page 345: ...Synergy Controller Technical Manual Revision H Page 345...
Page 346: ...Synergy Controller Technical Manual Revision H Page 346...