Synergy Controller Technical Manual, Revision H
Page 206
Ambient Device
This output is used when cooling is required with humidity control
Output is either Time Proportioning or On/Off
L7 Ambient Cooling Turn On
Percent cooling required to turn on the cooling
compressor
L8 Heat Ambient Cooling Turn Off
Percent heat required to turn off the cooling compressor
L9 Ramp Up Cooling
Temperature at which the cooling compressor is turned
off while heating
Control Parameters
Default Value:
Range:
Channel 2 Proportional Band Heating
42
0 - 50 Degrees C
Reset for Channel 2 Heating
0.02
0 - 9.9 Repeats/minute
Rate for Channel 2 Heating
0
0 - 9.9 Minutes
Cycle Time for Channel 2 Heating
1
1 - 60 Seconds
Rate Band for Channel 2 Heating
0
0 - 7 Seconds
Channel 2 Proportional Band Cooling
40
0 - 50 Degrees C
Reset for Channel 2 Cooling
0.1
0 - 9.9 Repeats/minute
Rate for Channel 2 Cooling
0
0 - 9.9 Minutes
Cycle Time for Channel 2 Cooling
7
1 - 60 Seconds
Rate Band for Channel 2 Cooling
0
0 - 7 Seconds
Summary of Contents for Synergy Compact
Page 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Page 71: ...Synergy Controller Technical Manual Revision H Page 71...
Page 106: ...Synergy Controller Technical Manual Revision H Page 106...
Page 123: ...Synergy Controller Technical Manual Revision H Page 123...
Page 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Page 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Page 188: ...Synergy Controller Technical Manual Revision H Page 188...
Page 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Page 294: ...Synergy Controller Technical Manual Revision H Page 294...
Page 312: ...Synergy Controller Technical Manual Revision H Page 312...
Page 345: ...Synergy Controller Technical Manual Revision H Page 345...
Page 346: ...Synergy Controller Technical Manual Revision H Page 346...