Synergy Controller Technical Manual, Revision H
Page 230
Page 230
Description
Command Usages
Command Syntax
Range,
Units
Command
Example
Response Example
Ch * Cool Reset
RS*C Set
= RS*C ARG1
0 - 09.999 Repeats / Minute
= RS1C .700
OK
RS*C Query
? RS*C
0 - 09.999 Repeats / Minute
? RS1C
0.070
Ch * Cool Rate
RT*C Set
= RT*C ARG1
0 - 09.999 Minutes
= RT1C 1
OK
RT*C Query
? RT*C
0 - 09.999 Minutes
? RT1C
1.000
Ch * Cool Cycle Time
CT*C Set
= CT*C ARG1
1 - 60 Seconds
= CT1C 7
OK
CT*C Query
? CT*C
1 - 60 Seconds
? CT1C
7.00
Ch * Cool Rate Band
RB*C Set
= RB*C ARG1
0 - 7 Seconds
= RB1C 4
OK
RB*C Query
? RB*C
0 - 7 Seconds
? RB1C
4.000
Ch * Cascade Enabled
CAS*_ENABLED Set
= CAS*_ENABLED ARG1
0 - Disabled, 1 - Enabled
= CAS1_ENABLED 1
OK
CAS*_ENABLED Query
? CAS*_ENABLED
0 - Disabled, 1 - Enabled
? CAS1_ENABLED
1
Ch * Cascade Sensor
CSS* Set
= CSS* ARG1
ARG1 - ID of the Sensor. 100 -
999.
= CSS1 120
OK
CSS* Query
? CSS*
See the user manual for numeric
codes.
? CSS1
120
Ch * Cascade High Limit
C*HL Set
= C*HL ARG1
- 200 to 500 C -326 to 932 F
= C1HL 200
OK
C*HL Query
? C*HL
- 200 to 500 C -326 to 932 F
? C1HL
200.00
Ch * Cascade Low Limit
C*LL Set
= C*LL ARG1
- 200 to 500 C -326 to 932 F
= C1LL -100
OK
C*LL Query
? C*LL
- 200 to 500 C -326 to 932 F
? C1LL
-100.00
Ch * Cascade Prop. Band
CPB*H Set
= CPB*H ARG1
0 to 400 C 0 to 752 F
= CPB1H 10
OK
CPB*H Query
? CPB*H
0 to 400 C 0 to 752 F
? CPB1H
Ch * Cascade Reset
CRS*H Set
= CRS*H ARG1
0 - 09.99 Repeats / Minute
? CRS1H
OK
CRS*H Query
? CRS*H
0 - 09.99 Repeats / Minute
? CRS1H
1.000
Ch * Cascade Rate
CRT*H Set
= CRT*H ARG1
0 - 09.99 Minutes
= CRT1H 1
OK
CRT*H Query
? CRT*H
0 - 09.99 Minutes
? CRT1H
1.000
Ch * Cascade Rate Band
CRB*H Set
= CRB*H ARG1
0 - 09.99 Minutes
= CRB1H 4
OK
CRB*H Query
? CRB*H
0 - 09.99 Minutes
? CRB1H
4.000
Ch * Cascade Pos. Deviation
Limit
C*HMAXDELTA Set
= C*HMAXDELTA ARG1
ARG1:
0-50C, 0 - 90F
= C1HMAXDELTA 10
OK
C*HMAXDELTA Query
? C*HMAXDELTA
0-50C, 0 - 90F
? C1HMAXDELTA
10.0
Ch * Cascade Neg. Deviation
Limit
C*LMAXDELTA Set
= C
*
LMAXDELTA ARG1
ARG1:
0-50C, 0 - 90F
= C1LMAXDELTA 20
OK
C*LMAXDELTA Query
? C*LMAXDELTA
0-50C, 0 - 90F
? C1LMAXDELTA
20.0
Ch * Heat PID
PID*H Query
? PID*H
0 - 100 %
? PID1H
0.0
Ch * Cool PID
PID*C Query
? PID*C
0 - 100 %
? PID1C
100.0
Ch * Cascade PID
CPID* Query
? CPID*
0 - 100 %
? CPID1
100.0
Ch * Low Limit
R*L Set
= R*L ARG1
- 200 to 500 C -326 to 932 F
= R1L -200
OK
Summary of Contents for Synergy Compact
Page 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Page 71: ...Synergy Controller Technical Manual Revision H Page 71...
Page 106: ...Synergy Controller Technical Manual Revision H Page 106...
Page 123: ...Synergy Controller Technical Manual Revision H Page 123...
Page 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Page 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Page 188: ...Synergy Controller Technical Manual Revision H Page 188...
Page 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Page 294: ...Synergy Controller Technical Manual Revision H Page 294...
Page 312: ...Synergy Controller Technical Manual Revision H Page 312...
Page 345: ...Synergy Controller Technical Manual Revision H Page 345...
Page 346: ...Synergy Controller Technical Manual Revision H Page 346...