SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Wet Bulb Sensor
WETB_SENID
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Dry Bulb Sensor
DRYB_SENID
Assign the sensor IDs for the two temperature sensors.
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Altitude – Torr\
WBDB_ALT
The Altitude – Torr Sensor parameters sets the pressure at the site to allow the controller to compensate the
humidity calculation for the pressure altitude.
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Wet Bulb Input Filter\
WBIN_FLT_ENABLED
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Wet Bulb Filter Max Delta\
WBIN_FLT_MAXD
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Wet Bulb Filter Weight\
WBIN_FLT_WT
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Dry Bulb Input Filter\
DBIN_FLT_ENABLED
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Dry Bulb Filter Max Delta\
DBIN_FLT_MAXD
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Dry Bulb Filter Weight\
DBIN_FLT_WT
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Wet Bulb Input Filter\
WBIN_FLT_ENABLED
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Wet Bulb Input Filter\
WBIN_FLT_ENABLED
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Wet Bulb Input Filter\
WBIN_FLT_ENABLED
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Wet Bulb Input Filter\
WBIN_FLT_ENABLED
SETUP\Calibration\Virtual Sensors\Wet Bulb Dry Bulb\Wet Bulb Input Filter\
WBIN_FLT_ENABLED
Wet-Bulb/Dry-Bulb Virtual Sensor Filter parameters
6.2.5.2 Virtual Kft Sensor
The Virtual Kft. sensor calculates Altitude in Kft (thousands of feet) from a pressure sensor scaled in Torr.
SETUP\Calibration\Virtual Sensors\Virtual KFt\Torr Sensor
VIRTKFTSEN
The Torr Sensor parameter is the sensor ID of the Torr sensor.
5.2.5.3 Virtual Pressure Sensor
The Virtual Pressure sensor combines the readings from two pressure sensors into one sensor to increase
the accuracy of the reading over a wide range.
Virtual Pressure Sensor
♦
Std. Range Pres. Sensor ID
♦
High Alt. Pres. Sensor ID
♦
Transfer Pres. Threshold
♦
Transfer Pres. Hysteresis
The Virtual Pressure sensor combines the readings
from two sensors into one sensor to increase the
accuracy of the reading over a wider range than
possible with a single sensor.
These settings specify the two sensor IDs and
control when the virtual sensor switches between
the two input sensors. (the transfer pressure
threshold and hysteresis which)
Summary of Contents for Synergy Compact
Page 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Page 71: ...Synergy Controller Technical Manual Revision H Page 71...
Page 106: ...Synergy Controller Technical Manual Revision H Page 106...
Page 123: ...Synergy Controller Technical Manual Revision H Page 123...
Page 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Page 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Page 188: ...Synergy Controller Technical Manual Revision H Page 188...
Page 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Page 294: ...Synergy Controller Technical Manual Revision H Page 294...
Page 312: ...Synergy Controller Technical Manual Revision H Page 312...
Page 345: ...Synergy Controller Technical Manual Revision H Page 345...
Page 346: ...Synergy Controller Technical Manual Revision H Page 346...