L-Value Descriptions
L-Values are parameters for the programmable logic that control processes in the Device Primitives. Flow
charts illustrating the Device Primitives are illustrated in
of this manual. Please
refer to the Device Primitives flow charts in conjunction with the definitions below when editing L-Values.
Thermal Shock Parameters
1L1 Ch1 Main Cooling Turn-On
Cooling output required to turn on channel 1 cooling. (0 to 100%)
1L2 Ch1 Main Cooling Turn-Off
Heat output required to turn off channel 1 main cooling. (-100 to 100%)
1L3 Ch1 Setpoint Transfer Setting
Temperature threshold for the artificial load output. (-100 to 100C, -148 to 212F)
1CTY Ch1 Chamber Type
Defines the controlling logic for channel 1. (CAP Tube System, Agree Logic, Burn-in Logic, XV Sys
Logic)
2L1 Ch2 Main Cooling Turn-On
Cooling output required to turn on channel 2 cooling. (0 to 100%)
2L2 Ch2 Main Cooling Turn-Off
Heat output required to turn off channel 2 main cooling. (0 to 100%)
2L3 Ch2 Setpoint Transfer Setting
Artificial load is enabled above this temperature threshold. (-100 to 100C, -148 to 212F)
2CTY Ch2 Chamber Type
Defines the controlling logic for channel 1. (CAP Tube System, Agree Logic, Burn-in Logic, XV Sys
Logic)
Temperature Humidity/Temperature Only
L3 Ch1 Main Cooling Turn-On
The low stage compressor is switched on above this PID Cooling output percentage. (0 to 100%)
L4 Ch1 Main Cooling Turn-Off
Percent heat required before turning off low stage compressor. (0 to 100%)
L6 Full Cooling Switch-Over
Full cooling is switched on at this temperature. (-100 to 100C, -148 to 212F)
L7 Ambient Cooling Turn-On
Percent cooling required that turns on the compressor. (0 to 100%)
L8 Heat Ambient Cooling Turn-Off
Percent heat required to turn off the compressor. (0 to 100%)
L9 Ramp-up Cooling
A temperature setpoint above this threshold turns off the compressor when heating. (-100 to 100C, -
148 to 212F)
Summary of Contents for Synergy Compact
Page 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Page 71: ...Synergy Controller Technical Manual Revision H Page 71...
Page 106: ...Synergy Controller Technical Manual Revision H Page 106...
Page 123: ...Synergy Controller Technical Manual Revision H Page 123...
Page 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Page 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Page 188: ...Synergy Controller Technical Manual Revision H Page 188...
Page 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Page 294: ...Synergy Controller Technical Manual Revision H Page 294...
Page 312: ...Synergy Controller Technical Manual Revision H Page 312...
Page 345: ...Synergy Controller Technical Manual Revision H Page 345...
Page 346: ...Synergy Controller Technical Manual Revision H Page 346...