Synergy Controller Technical Manual, Revision H
Page 86
Example 2
At low atmospheric pressures, the heaters in most altitude chambers are turned off so they don’t overheat
when convection cooling capacity is reduced. In this example we will create an alarm that senses Hi Res
Input 3 (Torr) and opens Relay 2 when the value is less than 30 Torr. This alarm is named “Heater Safety
Shutoff” and displays “Heater Safety Shutoff” when the threshold is reached.
Open the User Alarm folder and press the
Add Alarm
button on the Setup screen shown
at left.
Select the
Olympic
Module and
Analog 1
, the
Hi Resolution Analog input.
This screen shows the Sensor code for the
Olympic Module and Analog input 1.
Since we want the alarm to trigger when the
pressure is less than 30 Torr, we select the
Summary of Contents for Synergy Compact
Page 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Page 71: ...Synergy Controller Technical Manual Revision H Page 71...
Page 106: ...Synergy Controller Technical Manual Revision H Page 106...
Page 123: ...Synergy Controller Technical Manual Revision H Page 123...
Page 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Page 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Page 188: ...Synergy Controller Technical Manual Revision H Page 188...
Page 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Page 294: ...Synergy Controller Technical Manual Revision H Page 294...
Page 312: ...Synergy Controller Technical Manual Revision H Page 312...
Page 345: ...Synergy Controller Technical Manual Revision H Page 345...
Page 346: ...Synergy Controller Technical Manual Revision H Page 346...