Synergy Controller Technical Manual, Revision H
Page 216
If your cascade control is not registered you will
encounter the screen on the left. Press the
Registration Key text box to open the
alphanumeric keypad. Enter your registration
number. The cascade registration number is
available from Tidal Engineering or your chamber
manufacturer.
16.2.2 Configuring Cascade Software
16.2.2.1 General
Several settings and parameter options control the Cascade loop. In addition, the air temperature loop PID
constants will usually require additional tuning, especially with the Cascade Proportional Band setting. The
PID / Parameter Option Chart below shows the recommended and default settings for Cascade algorithm.
PID / Parameter Option Chart
PID
Parameter
Recommended
Default
Cascade
Enabled
Enabled
Disabled
Cascade
Sensor Select
As required
120, RTD2
Cascade
High Limit (Temp)
200
200
Cascade
Low Limit (Temp)
-100
-100
Cascade
Positive Deviation Limit
5
5
Cascade
Negative Deviation Limit
5
5
Cascade
Proportional Band
7.0
7.0
Cascade
Reset
0.02
0.02
Cascade
Rate
0.00
0.00
Cascade
Rate Band
0.00
0.00
Heat
Proportional Band
14.0
7.0
Cool
Proportional Band
10.0
5.0
In order to view and change the Cascade PID / Parameter settings, press the
SETUP
Screen Navigation key
and go to the screen below. For Inner Loop settings, go to the
PID Settings\PID Ch1\Heat or Cool
folder.
Summary of Contents for Synergy Compact
Page 14: ...Synergy Controller Technical Manual Revision H Page 14 2 0 SPECIFICATIONS 2 1 Data Sheet...
Page 71: ...Synergy Controller Technical Manual Revision H Page 71...
Page 106: ...Synergy Controller Technical Manual Revision H Page 106...
Page 123: ...Synergy Controller Technical Manual Revision H Page 123...
Page 141: ...Synergy Controller Technical Manual Revision H Page 141 TE1151 6 Triac Output Board Schematic...
Page 142: ...Synergy Controller Technical Manual Revision H Page 142 TE1708 6 Relay Board Schematic...
Page 188: ...Synergy Controller Technical Manual Revision H Page 188...
Page 274: ...Synergy Controller Technical Manual Revision H Page 274 Synergy Controller Step Syntax...
Page 294: ...Synergy Controller Technical Manual Revision H Page 294...
Page 312: ...Synergy Controller Technical Manual Revision H Page 312...
Page 345: ...Synergy Controller Technical Manual Revision H Page 345...
Page 346: ...Synergy Controller Technical Manual Revision H Page 346...