background image

Page 4 

 

Other parts of the 

STAR-BRAKE 

serve to control and 

coordinate the action of the braking current, to form a 
complete braking system. These are described in the 
balance of this section. 

 

8.2  Detail Description 

 

8.2.1 

Sensing 

 

This is the part of the system that determines when 
braking is required. It consists of circuitry which detects 
when the motor is 

ON 

by sensing the current flowing 

through the internal interlock to the starter contactor. 
When this current is removed (starter contactor is 
disengaged) the brake is activated. 

 

Note: leakage current in the magnetic starter control loop 
when the starter is disengaged may be interpreted by the 
sensor as a motor run condition, not allowing the brake to 
pull in. 

 

8.2.2 

Interlock 

 

Once an "OFF" condition is determined by the sensor, the 
interlock is opened. This prevents the motor from being 
re-started while the braking function is in progress. The 
interlock will not be re-established until braking has been 
completed. 

 

8.2.3 

Logic and Timing 

 

This section initiates the flow of DC power after the 
braking contactor has been closed; removes the DC 
power and opens the braking contactor at the end of 
braking; and re-closes the interlock as the last item in the 
braking cycle, restoring control to the motor starter. 

 

8.2.4 

DC Power and Control 

 

Under control of the Timing section, this block has the 
function of setting up the path for the flow of DC current to 
the motor, and for rectifying power from the AC input 
supply for DC braking. 

 

Rectification is done by means of a "Controlled Rectifier," 
or SCR. This device conducts for a controllable part of 
each AC power line cycle. By setting the phase angle 
allowed for conduction via the Torque pot, the amount of 
DC current produced for braking can be controlled. 

 

The Controlled Rectifier is not turned ON until after the 
braking contactor has closed. It is turned OFF before this 
contactor is allowed to open. In this way, the contactor is 
never called on to switch under load, and the contacts 
therefore experience no wear or arcing - even though they 
are carrying DC. This is why it is imperative that the 
braking cycle be allowed to run to completion in the 
normal way. 

9.  IF YOU HAVE A PROBLEM 

 

9.1  Preliminary  Checks 

 

Check for possible damage in shipping, if so, notify the 

freight carrier. 

 

No adjustments are provided or required other than those 
described in Section 7. 

 

Should a system fail to perform properly, be sure to check 
the wiring first. Also, be certain that the power  line voltage  
is present and correct.  (For  instance,  there  should be 
equal voltages between any two leads of a three phase 
power  line, and these should be in the correct  nominal 
range for the 

STAR-BRAKE.) 

 

If the system has previously been operating properly, it is 
also a good idea to check the fuses, and that the 
adjustments of the three controls, TIME, TORQUE and 
OVERLOAD have not been tampered with. Note: 230 volt 
units operated from 208 volts will produce somewhat 
lower torque. Consult the factory if this is a problem. 

 

If there is a problem on initial installation, or if the brake 
should fail to function properly, the following checks 
should be made: 

 

9.2  Motor Will Not Start 

 

1.  Verify that there is normal line voltage across Termi- 

nals L1, L2, L3. Note: 230 volt units operated from a 
208 volt line may not allow the starter to engage. (208 
volt Models are available.) 

 

2.  Verify that the START and STOP switches are wired 

properly. AC control voltage should be present across 
START switch. When the switch is pressed you 
should read ZERO volts.  When the START button 
and the STOP button are pressed simultaneously, you 
should read AC control voltage across the STOP 
switch. 

 

3.  Make sure that the overload has not tripped. In case 

the overload has tripped, wait 3 to 7 minutes and then 
push the reset button located on the top of the over- 
load. NOTE: Frequent starting and stopping, (espe- 
cially with high inertia motor loads) can cause nui- 
sance tripping of the overloads and fuses. 

 

4.  Make sure that the overload adjustment has not been 

tampered with. 

Summary of Contents for AMBITECH STAR-BRAKE

Page 1: ...STAR BRAKE Motor Starter Electronic Brake Instructions...

Page 2: ...Instructions Motor Starter Electronic Brake CAUTION Disconnect and lock out power to Star Brake Terminals 1 2 and 3 before servicing...

Page 3: ...Overload 3 7 2 2 Brake Adjustment 3 8 DESCRIPTION OF BRAKING FUNCTION 3 8 1 Basic Concept 3 8 2 Detail Description 4 8 2 1 Sensing 4 8 2 2 Interlock 4 8 2 3 Logic and Timing 4 8 2 4 DC Power and Contr...

Page 4: ...mage not covered by the warranty POWER LINE INTERRUPTION The STAR BRAKE uses AC line power to achieve its braking action Thus a power failure or disconnect or the opening of a fuse will simply let the...

Page 5: ...g 1 Connect a dry momentary normally closed Stop pushbutton between Terminals S1 and S2 2 Connect a dry momentary normally open Start pushbutton between Terminals S2 and S3 Note If a programmable cont...

Page 6: ...e Braking action is indicated by a slight hum of the motor as well as the red LED being lit 6 Adjust TIME control so that braking hum stops and LED goes out after the motor stops Note As the motor hea...

Page 7: ...en In this way the contactor is never called on to switch under load and the contacts therefore experience no wear or arcing even though they are carrying DC This is why it is imperative that the brak...

Page 8: ...he warranty is VOID if the unit has been tampered with without express permission if fuses of an NOTE Fuses in the STAR BRAKE are designed to incorrect type or rating have been used or for any Protect...

Reviews: