Pag. 11/15
0CAR6IN019124_Manual_GLH110_Rev_0.3
Hydraulic Plant 7 (ConF = 7)
Name
Symb
ol
Pins
Fireplace Pump
P1
3 – 4
PWM1
19 - 16 o 14
Diverter Valve
P2
5 – 6 – 7
Boiler Integration
P3
8 – 9 – 10
Service / Air Damper*
P4
11 – 12
Fireplace Probe
S1
13 – 14
Probe Boiler Sanitary
(DHW)
S2
15 – 16
Probe/Ambient Thermostat
Pressure Sensor
S3
16 – 17 – 18
7.7.1 Parameters
Cod.
Led
Description
U.
Min. Def. Max
A01
Fireplace Pump minimum temp. Thermostat
°C
20
35
90
A02
Thermostat Diverter Valve
°C
20
45
90
A03
Boiler Integration Thermostat
°C
20
45
90
A09
Service Thermostat
°C
20
50
90
A18
Sanitary (DHW) Boiler Thermostat
°C
20
50
90
b01
Ambient Probe Thermostat
°C
5
20
50
d01
+
Differential Thermostat
Δ
(S1-S2)
°C
2
5
20
7.7.2 Operating Principle
S1
S2
Δ (S1-S2) Management
P1 P2
S1< 5°C [
A06
]
Deicing
ON OFF
5° <S1< 30°
A06 <S1< A01
Fireplace OFF
OFF OFF
30° <S1< 45°
A01 <S1< A02
T2< 50° [
A18
]
Δ< 5° [
d01
]
OFF OFF
Δ> 5° [
d01
]
Sanitary (DHW)
ON OFF
T2> 50° [
A18
]
OFF OFF
45° <S1< 80°
A02 <S1< A07
T2< 50° [
A18
]
Δ< 5° [
d01
]
Sanitary (DHW)
Priority
OFF OFF
Δ> 5° [
d01
]
ON OFF
T2> 50° [
A18
]
Heating
ON ON
S1> 80° [
A07
]
Safety
ON ON
S1> 45° [
A03
]
Integration
9 - 10 OPEN
OFF
P3
S1> 75° [
A05
]
See Par. 5.11
Air Damper
OFF
P4
S1> 45° [
A09
]
See Par. 5.10
Service
ON
* Se P06=3
Hydraulic Plant 8 (ConF = 8)
Name
Symb
ol
Pins
Fireplace Pump
P1
3 – 4
PWM1
19 - 16 o 14
Heating Pump
P2
5 – 6 – 7
PWM2
20 - 16 o 14
Boiler Integration
P3
8 – 9 – 10
Service / Air Damper*
P4
11 – 12
Fireplace Probe
S1
13 – 14
Probe Boiler Sanitary
(DHW)
S2
15 – 16
Probe/Ambient Thermostat
Pressure Sensor
S3
16 – 17 – 18
7.8.1 Parameters
Cod.
Led
Description
U.
Min. Def. Max
A01
Fireplace Pump minimum temp. Thermostat
°C
20
35
90
A04
Heating Pump Thermostat
°C
20
45
90
A03
Boiler Integration Thermostat
°C
20
45
90
A09
Service Thermostat
°C
20
50
90
A18
Sanitary Boiler Thermostat
°C
20
50
90
b01
Ambient Probe Thermostat
°C
5
20
50
d01
+
Differential Thermostat
Δ
(S1-S2)
°C
2
5
20
7.8.2 Operating Principle
S1
S2
Δ (S1-S2) Management
P1 P2
S1< 5°C [
A06
]
Deicing
ON OFF
5° <S1< 30°
A06 <S1< A01
Fireplace OFF
OFF OFF
30° <S1< 45°
A01 <S1< A02
T2< 50° [
A18
]
Δ< 5° [
d01
]
OFF OFF
Δ> 5° [
d01
]
Sanitario
ON OFF
T2> 50° [
A18
]
OFF OFF
45° <S1< 80°
A02 <S1< A07
T2< 50° [
A18
]
Δ< 5° [
d01
]
Sanitary (DHW)
Priority
OFF OFF
Δ> 5° [
d01
]
ON OFF
T2> 50° [
A18
]
Heating
OFF ON
S1> 80° [
A07
]
Safety
ON ON
S1> 45° [
A03
]
Integration
9 - 10 OPEN
OFF
P3
S1> 75° [
A05
]
See Par. 5.11
Air Damper
OFF
P4
S1> 45° [
A09
]
See Par. 5.10
Service
ON