background image

 

Pag. 2/15  

0CAR6IN019124_Manual_GLH110_Rev_0.3

 

 

4. 

Control Panel: USE AND FUNCTIONS

 

 

ON/OFF  

Exit the Menu 

Gr

ill

 Service

 

Shutter Manual Start 

K1

 

 

 

 

 

 

K3

 

Scroll/Increase 
Pump1 Test 
Probes Menu 

Enter User Menu 

SET 

Shower Key 

K2

 

 

 

K4

 

Scroll/Decrease 
Pump2 Test  
Probes Menu 

 

Fig. 3 Main Screen

 

  S1 Probe Temperature 

 

S1 Probe Displayed 

 

P1 Output Activated 

 

S2 Probe Displayed 

 

P2 Output Activated 

 

S3 Probe Displayed 
Fashing: Ambient Thermostat open 

 

P3 Output Activated 

 

ON: 

 

Flow Switch Closed 

Fashing:  

Shower Function Activated 

 

P4 Output Activated 

 

5. 

FUNCTIONALITIES 

 

IGNITION/EXTINGUISHING 

Controller Ignition/Extinguishing is perforemd by applying prolongued pressure to 

K1 

key 

 

OFF-mode is displayed by 

K1

 key being turned-on

 

 

When the controller is turned on, the following messages will appear 

o

 

Product Code      

t002

 

o

 

Product Revision          

r 0.1

 

o

 

Configuration

              CF01

 

 

PROBE DISPLAY 

The display shows the correct temperature sensor value 

S1

 (

S1

 led is lit up). 

 

To enter the probe menu press either 

K4

 or

 K3

, the temperature of Probe 

S2

 is displayed (

S2 

Led flashes) or 

S3

 (

S3

 Led 

flashes) 

 

By pressing 

K3

 or 

K4

 it is possible to scroll and check other connected probes 

 

To exit the Menu press 

K1

 or wait 10 seconds 

 

If the probe reading is below the minimum range of the sensor the message 

Lo 

appears 

 

If the probe reading is above the maximum range of the sensor the message 

Hi 

appears 

 

SAFETY FEATURE 

When this function is activated; 

P11

=

1

, it starts a heat disposing process to remove excess heat buildup of the fireplace 

The management of the safety feature is expalined in the plumbing/hydraulic schematic drawing parapraphs

 

 

ALARM FUNCTION 

If the temperature measured by 

Sensor S1

 exceeds the value of the thermostat alarm 

A08

 

 

An audible and visual signal is activated (the temperature flashes on the Display) 

 

SILENCE 

Function: The audible signal can be turned off for 5 minutes by pressing any key. If the controller remains in 

the alarm condition the audible signal will start again. 

 

ANTIFREEZE FUNCTION 

If the temperature measured by 

Probe S1

 falls below the value of the Antifreeze Thermostat 

A06

 

 

The output for Pump 

P1

 is turned on for 

t01 

time

 

at intervals of 

t02 

time 

 

The display will show the writing 

ICE

 

 

PUMP P1 ANTISEIZE FUNCTION  

If Pump 

P1 

remains inactive, also while OFF, for a time greater than Timer 

t05

 

 

The output for Pump 

P1

 is turned-on for 

t04

 seconds 

 

The display will show the writing 

bLP

 

 

STANDBY FUNCTION 

If the controller is 

OFF

,

 

and in 

ALARM

ANTIFREEZE

 or 

ANTISEIZE FUNCTION 

of Pump 

P1

 

 

The controller automatically turns itself 

ON 

 

 

At the end of 

ANTIFREEZE

 or 

ANTISEIZE of Pump P1

 functions, the controller will turn itself 

OFF

 

Al the end of 

ALARM 

function the controller will remain 

ON

 

 

Summary of Contents for GLH110

Page 1: ...85 25 C 2 INSTALLATION Make sure that the Main Power Supply is OFF prior to installing the device Install the product in a dry environment with proper climatic conditions Insert a bipolar main switch compliying to local regulations Avoid coupling the probe cables with these of power Use for wiring cables with conductors of appropriate section and in according the rules Position the probes to detec...

Page 2: ...nsor the message Lo appears If the probe reading is above the maximum range of the sensor the message Hi appears SAFETY FEATURE When this function is activated P11 1 it starts a heat disposing process to remove excess heat buildup of the fireplace The management of the safety feature is expalined in the plumbing hydraulic schematic drawing parapraphs ALARM FUNCTION If the temperature measured by S...

Page 3: ...NU Fireplace Probe P01 0 NTC10K P01 1 NTC100K P01 2 PT1000 DHW Boiler Probe Tall Buffer P02 0 NTC10K P02 1 NTC100K P02 2 PT1000 Short Buffer Probe P03 0 NTC10K P03 1 NTC100K P03 2 PT1000 Ambient Probe P04 0 NTC10K P04 1 NTC100K P04 2 PT1000 Manifold Probe P17 0 NTC10K P17 1 NTC100K P17 2 PT1000 S3 INPUT CONFIGURATION Parameter P05 can be enabled to mange the following P05 0 S3 input DISABLED P05 1...

Page 4: ...WM Manual The PWM duty cycle which determines the speed of the pumps is set with the following parameters U06 if PWM1 with Heating profile Fireplace Pump U16 if PWM2 with Heating profile Heating Pump U26 if PWM2 with Solar profile Solar manifold Pump Automatic PWM In relation to the type of pump the PWM duty cycle is calculated on the basis of the temperature of the fireplace probe high Buffer Tan...

Page 5: ... 45 90 C Service Thermostat on Fireplace probe A09 20 50 90 C Valve Thermostat for DHW priority A24 20 70 90 C Thermostat to activate Integration on Fireplace probe A03 20 45 90 C Thermostat Integration Buffer Tank on High Buffer Tank Probe A19 20 45 90 C Heating Pump Thermostat on Fireplace probe A04 20 45 90 C Service Thermostat on Fireplace probe A09 20 50 90 C Heating Pump Thermostat on High B...

Page 6: ...esis Thermostat of Integr Buffer Tank on High Buffer Tank Probe IA19 0 2 20 C Hysteresis Thermostat of Buffer Comfort on High Buffer Tank probe IA20 0 2 20 C Hysteresis Thermostat of High Temp on High Buffer Tank probe IA23 0 2 20 C Hysteresis Thermostat of Valve for DHW priority IA24 0 2 20 C Hysteresis Thermostat of Manifold Pump Activation IA33 0 2 20 C Hysteresis Thermostat of ANTIFREEZE Therm...

Page 7: ...ycle at Minimum Speed HEATING profile U11 0 85 100 Percentage of PWM2 Duty Cycle at Maximum Speed HEATING profile U12 0 5 100 Percentage of PWM2 Duty Cycle in Antifreeze HEATING profile U13 0 0 100 Percentage of PWM2 Duty Cycle in Safety HEATING profile U14 0 0 100 Percentage of PWM2 Duty Cycle in Antiseize HEATING profile U15 0 0 100 Percentage of PWM2 Duty Cycle in Modalità Manual HEATING profil...

Page 8: ...F P2 P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 2 ConF 2 Name Symbol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Valve P2 5 6 7 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 2 1 Parameters Cod Led Description U Min Def Max A01 Fi...

Page 9: ...A03 Integration 9 10 OPEN OFF P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 4 ConF 4 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Heating Pump P2 5 6 7 PWM2 20 16 o 14 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 4 1 Pa...

Page 10: ... A03 Integration 9 10 OPEN OFF P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 6 ConF 6 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Heating Pump P2 5 6 7 PWM2 20 16 o 14 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 6 1 P...

Page 11: ...ON S1 45 A03 Integration 9 10 OPEN OFF P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 8 ConF 8 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Heating Pump P2 5 6 7 PWM2 20 16 o 14 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Probe Boiler Sanitary DHW S2 15 16 Probe Ambient Thermostat Pressure Sens...

Page 12: ...5 2 e S3 Open o P05 3 e S3 20 b01 OFF S2 45 A19 Integration 9 10 OPEN OFF P3 S1 75 A05 See Par 5 11 Air Damper OFF P4 S1 45 A09 See Par 5 10 Service ON Se P06 3 Hydraulic Plant 10 ConF 10 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Manifold Pump P2 5 6 7 PWM2 20 16 o 14 Boiler Integration P3 8 9 10 Service Air Damper P4 11 12 Fireplace Probe S1 13 14 Buffer Probe S2 15 16 Manifold Prob...

Page 13: ... o Shower ON Sanitary DHW OFF OFF S1 80 A07 Safety ON ON S1 45 A02 Sanitary DHW ON P2 S1 45 A03 Integration 9 10 OPEN OFF P3 Hydraulic Plant 12 ConF 12 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Diverter Valve P2 5 6 7 Boiler Integration P3 8 9 10 Heating Pump P4 11 12 PWM2 20 16 o 14 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 ...

Page 14: ...itary DHW ON P2 S1 45 A03 Integration 9 10 OPEN OFF P3 Hydraulic Plant 14 ConF 14 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Diverter Valve P2 5 6 7 Boiler Integration P3 8 9 10 Heating Pump P4 11 12 PWM2 20 16 o 14 Fireplace Probe S1 13 14 Flow Switch S2 15 16 Probe Ambient Thermostat Pressure Sensor S3 16 17 18 7 14 1 Parameters Cod Led Description U Min Def Max A01 Fireplace Pump m...

Page 15: ...0 Service ON S3 45 A19 Integration 9 10 Open OFF P3 S3 45 A17 Heating ON P4 Se P06 3 Hydraulic Plant 16 ConF 16 Name Symb ol Pins Fireplace Pump P1 3 4 PWM1 19 16 o 14 Valve P2 5 6 7 Boiler Integration P3 8 9 10 Heating Pump P4 11 12 PWM2 20 16 o 14 Fireplace Probe S1 13 14 Buffer Probe Basso S2 15 16 Buffer Probe Alto S3 16 17 7 16 1 Parameters Cod Led Description U Min Def Max A01 Minimum temp P...

Reviews: