Pag. 5/15
0CAR6IN019124_Manual_GLH110_Rev_0.3
SOLAR Profile
On the basis of this profile it is advisable to set
the PWM duty cycle parameters as shown
below:
PWM2
Vmin: U01 >= 15%
Vmax: U02 <= 95%
In the following conditions the PWM can be setup with the following parameters:
ANTIFREEZE
:
U03, U13 e U23
SAFETY
: U04, U14 e U24
ANTISEIZE
:
U05, U15 e U25
6.
MENU’
6.1
MAIN MENU
To enter into the main menu simply
click
on
K2
key:
Keys
K3
and
K4
are used to scroll through various parameters signaled by the corresponding flashing led.
Press
K2
key to modify (the led remains solid while value flashes).
Keys
K3
and
K4
are used to change the parameter value.
Press
K2
to save the new value.
Press
K1
to exit without saving.
Press
K1
again to exit the Menu or wait 30 seconds.
Led
Description
Code
Min
Set
Max
U.M.
Low Temp. Thermostat for Fireplace Pump
A01
20
35
90
[°C]
Diverting Valve Thermostat on Fireplace probe
A02
20
45
90
[°C]
Heating Pump Thermostat on Fireplace probe
A04
20
45
90
[°C]
Heating Pump Thermostat on high Buffer Tank probe
A17
20
45
90
[°C]
Service Thermostat on Fireplace probe
A09
20
50
90
[°C]
Valve Thermostat for DHW priority
A24
20
70
90
[°C]
Thermostat to activate Integration on Fireplace probe
A03
20
45
90
[°C]
Thermostat Integration Buffer Tank on High Buffer Tank Probe
A19
20
45
90
[°C]
Heating Pump Thermostat on Fireplace probe
A04
20
45
90
[°C]
Service Thermostat on Fireplace probe
A09
20
50
90
[°C]
Heating Pump Thermostat on High Buffer Tank probe
A17
20
45
90
[°C]
DHW Boiler Thermostat on S2
A18
20
50
90
[°C]
Buffer Comfort Thermostat on High Buffer Tank probe
A20
20
60
90
[°C]
Ambient Probe Thermostat on S3
b01
5
20
50
[°C]
+
Differential Thermostat Fireplace-Boiler DHW/Buffer
d01
5
20
2
[°C]
6.2
INSTALLER MENU
Only QUALIFIED PERSONEL must access this MENU
, because if the set parameters are changed this could make the
product completely unsuitable for the application.
To enter into the INSTALLER MENU press at the same time
K2
and
K4
keys for 3 seconds.
To scroll through the parameter codes use
K3
and
K4
keys.
To view the value of a parameter and to enter modification mode press
K2
key.
To modify the value press
K3
and
K4
keys.
To save the new value press
K2
key.
To exit without saving press
K1
key.
Press
K1
again to exit the Menu or wait 60 seconds.