Pellet Modality
Off
Timer
Control Thermostats
Combustion
Heating
Resistance
Fan
Auger
P71
≠4 and
P74
,
P75
,
P76
≠18
exhaust temp.>
Th01
Thermostat
goes in Extinguishing if
the
system was previously in Pellet
modality
OFF
OFF
OFF
P71
=4 or
P74
,
P75
,
P76
=18 Light Flame >
L00
Thermostat
water temp.>Thermostat
Th25
goes in Block
Check Up
Timer
Control Thermostats
Combustion
Heating Resistance
Fan
Auger
T01
P71
≠4 and
P74
,
P75
,
P76
≠18
Si exhaust temp.>
Th09
and previously the
system was in Pellet Mode
goes in Run Mode
Max speed
OFF
OFF
Si exhaust temp.>
Th01
and previously the
system was in Wood or Combi Mode
goes in Ignition Recovery
P71
=4 or
P74
,
P75
,
P76
=18
If Light flame > Thermostat
L01
goes in Run Mode
If Water Temp. > (
Boiler Thermostat
–
Ih24
)
and
A27
=0
goes in Standby
Control when
T01
expires
goes in Ignition
Ignition
The state has some sub-phases and the current one is saved by the system.
Preheating
Timer
Control Thermostats
Combustion
Heating Resistance
Fan
Auger
T02
P71
≠4 and
P74
,
P75
,
P76
≠18
exhaust temp.>
Th09
Thermostat
goes in Run Mode
U01
OFF
ON
P71
=4 or
P74
,
P75
,
P76
=18
Light flame >
L01
Thermostat
goes in Run Mode