TESTING SHUTDOWN
TS4-L, TS4-O, and TS4-S (includes TS4-R and TS4-A add-on versions)
with Cloud Connect Advanced (CCA) and TAP are a solution to
meet module-level shutdown requirements.
TS4 units with the shutdown feature automatically enter shutdown
mode when the CCA is switched off and resume energy production
when power is restored to the CCA.
Wait 30 seconds after shutdown activation before disconnecting DC
cables or turning off DC disconnect.
39
Test your shutdown system by switching off the AC power to the CCA.
TS4 units with the shutdown feature will reduce their output to 0V when the
CCA is powered off.
The CCA power supply MUST be on the same AC branch circuit as the
inverter to meet shutdown requirements.