Connecting to TCH A2 infrared heater
1. Infrared heater and control unit are designed to connect to the AC mains with 220V
single-phase voltage (allowable voltage uctuations from 198V to 242V).
2. To connect the control unit to the electric mains and a heater, unscrew 2 screws behind
the unit and remove the top cover.
3. The control unit is connected in compliance with the diagram, speci ed in Fig. 5, on the
case of an infrared heater and terminal block of the control unit.
4. The unit must be connected to the electric mains by the cable with strand cross section
not less than 1.5 mm2 and along with installation in the electric mains of a circuit breaker
with rated current not less than 16A.
Fig
.
4
10
w
ww.timberk.
com
remote control block
700W/1000W/
1500W/2000W
Heating element
Heating element
N
L2
PE
L
L1
N
R1
OUT
IN
R2
R3
L3
L2
L1
N
Relay
K
Relay
K
N
220V~
N
O
1
2
Summary of Contents for TMS 08.CH
Page 15: ...TMS08 CH TCHA1N TCHA2 Timberk 1 15 www timberk com ...
Page 16: ... 2 3 TCH A2 4 1 16 www timberk com ...
Page 18: ...Рис 1 18 www timberk com 38 135 ...
Page 19: ...6 2 1 2 3 2 1 POWER 2 3 4 4 19 www timberk com ...
Page 20: ... 3 1 2 1 2 3 20 www timberk com ...
Page 21: ...1 LCD 2 3 4 5 ON OFF 6 MODE 7 HEAT TCHA2 800 1100 21 www timberk com 1 5 2 7 6 4 3 Рис 3 ...
Page 22: ...7 1 1 2 1 3 1 4 1 8 1 220 198 242 2 22 www timberk com 3 1000 ...
Page 24: ...24 www timberk com Рис 11 Рис 12 TCH A1N L2 L1 11 ...
Page 28: ...5 ON OFF 10 28 www timberk com ...
Page 31: ...8 12 Timberk Timberk 24 Timberk Timberk Timberk Timberk 31 www timberk com ...
Page 32: ... Timberk 32 www timberk com ...
Page 33: ...Timberk Timberk 24 а ...
Page 34: ......
Page 35: ...35 www timberk com ...
Page 36: ...ÀÂ71 www timberk com ...