PDFM362 PDFM361 can also be
controlled by the infrared remote
controller IR10. As well as allowing
remote setting of times and light level
the IR10 also enables continuous
operation for 8 hours in ON or OFF
modes as well as continuously in
detection mode controlled by or
independent of light level.
The IR10 is invaluable during
commissioning enabling changes to
be made without resorting to ladders.
Further to this the IR10 can download
stored settings from one sensor to
additional sensors in the same area.
3.3.2 (cont). The protection covers have teeth (see Fig. 8-A) giving
a degree of cable clamping if power and load are connected by
individual wires (0.8 –1.8mm dia.).
If connection is by cable (9 – 11mm dia.) then use of a coarse rat-tailed
file to open out as many of the holes as necessary using the markings
on the inside of the protection cover as an approximate guide
(see Fig. 8-B).
Referring it to the appropriate wiring diagram insert the wires into the
correct screw terminals and tighten fully. Then plug the sensor lead into
SENSOR A socket only.
Use the coarse rat-tailed file to open a single hole (smaller than that
above) in the remaining protection cover to take the sensor cable with
a degree of strain relief. Secure down the protection covers.
3.3.3 Feed the wires/cables followed by the power unit through the
65mm dia. ceiling hole (see Fig. 9).
4.1.1 TIME control adjustment
These are delay times between the sensor being triggered and the
controller switching off assuming no further detections are made.
If there are additional detections the time delay applies from the
latest detection.
PDFM362:
TIME 1: Adjustable from 5 sec. to 20 min. (lighting). (Extendable to
30 min. and 60 min. when in use with the IR10 remote controller).
TIME 2: Adjustable from 10 sec. to 60 min. (HVAC).
PDFM361:
TIME: Adjustable from 5 sec. to 20 min. (lighting). (Extendable to
30 min. and 60 min. when in use with the IR10 remote controller).
4.1.2 LUX control adjustment
The LUX level below which the sensor will operate is adjustable from
10 LUX (operation only after dusk) to 2000 LUX (operation at any
light level).
4.1.3 METER control adjustment
This control sets the diameter of detection coverage at floor level.
Assuming a ceiling height of 2.5m at the + end of the scale the
coverage diameter will be 7m, at the – end of the scale the coverage
diameter will be 1m.
The affect of METER control at other ceiling heights is shown in section 3.1.
4.2 Test Mode
4.2.1 Sensor warm up
The detector will take a minimum of 60 seconds to warm up when the
power is connected to it for the first time or if the power is being
re-connected after being turned off.
During this period load I and the sensor LED will both be on. After the
warm up is finished the sensor will revert to operation according to the
settings of the controls on the sensor body.
4.2.2 LED function
There is a red LED (see Fig. 12) built into the sensor and visible through
the PIR lens that shows the status of the loads and enables testing to be
carried out without the loads
being connected.
If the IR10 remote controller
is in use the LED will flash to
give confirmation of the
commands and adjustments
made by the IR10.
3.3.4 Force the spring clips back until they can feed into the ceiling hole
(see Fig. 10-A) and then push the sensor upwards into place so that its
flange fits tightly against the ceiling (see Fig. 10-B).
Fig. 8-A
Fig. 8-B
Fig. 9
Fig. 10-A
Fig. 10-B
4
Test and Operation
5
Troubleshooting
6
Optional Remote Control – IR10
4.1 Time, LUX and Meter Controls
Following marked values (excepting TEST and
) are approximate,
the values are continuously adjustable over the control range
(see Fig. 11-A & Fig. 11-B).
Fig. 11-A (PDFM362 control dials)
Fig. 11-B (PDFM361 control dials)
4.2.3 Adjusting sensor head
The sensor head can be tilted by as much as 30º off axis as shown
in Fig. 13A. This can be achieved by using a flat blade screwdriver
as shown in Fig. 13B.
Fig. 13C shows the tilt angle markings on the sensor body. The tilt
angle is read off against the edge of the mounting flange.
Fig. 13D shows the detection coverage for various tilt angles.
The tilt angle can be used in conjunction with rotation of the
sensor head within the flange up to 350º to give the required
coverage in any direction. The markings on the sensor mounting
flange (see Fig. 13E) giving 30º per division provide a useful
way of adjusting angular position.
When the PDFM362 PDFM361 is not working as expected go
through the troubleshooting guide below.
4.2.4 Walk test
Turn supply on and wait at least 60 seconds for the system to
settle down.
Turn Time 1 control to the Test position. This means that the sensor
LED and load I will turn on for 2 seconds after triggering and then
be off for 3 seconds after which the sensor can be re-triggered.
The triggering is independent of light level.
The installer should move around in the detection area to establish
that it is all covered. If necessary the tilt and rotation of the sensor
should be adjusted, after which the area should be walk tested
again to confirm coverage is as required.
To confirm that load 2 (HVAC) is operating correctly for a
PDFM362, carry out the following:-
Turn LUX (light level) to its minimum value (10 lux) to stop
load 1 (lights) from turning on. Then turn TIME 2 (HVAC) to
minimum value (10s) and carry out a limited walk test to
confirm correct operation of load 2.
Fig. 12
Fig. 13A
Fig. 13B
Fig. 13C
Fig. 13D
Fig. 13E
Problem
Possible
Suggested
Cause
Solution
Problem
Possible
Suggested
Cause
Solution
Lighting or
HVAC does not
turn off.
LED does not
turn on.
Nuisance
triggering.
Lights do not
turn on.
1. Incorrect time setting.
2. Incorrect wiring.
1. Out of detection range.
2. Power supply not on.
3. ‘TIME’ knob setting
isn’t on ‘Test’.
4. Incorrect wiring.
There are heat sources,
HVAC vents/fans,
highly reflective surfaces
or anything which may
be swayed by air
movement within the
detection coverage.
1. Power is not turned on.
2. Incorrect control
dial setting.
3. Incorrect wiring.
4. Faulty load.
1. Check that the correct delay
time is set on either TIME 1
or TIME 2 control dial.
Then determine if
nuisance triggering is
keeping the unit turned on.
2. Make sure supply and
load wires are connected
correctly.
1. Walk within the effective
detection range.
2. Switch the power on.
3. Turn the control position
to ‘Test’.
4. Refer to wiring diagrams
(Fig. 3 to Fig. 5).
Avoid aiming the sensor
toward any heat sources,
such as air conditioners,
electric fans, heaters or any
highly reflective surfaces.
Make sure there are no
swaying objects within the
detection coverage.
1. Switch on the power.
2. Check if control dials are
set to the correct position,
then supply the power to
check if the LED will turn on.
3. Refer to wiring diagrams
(Fig. 3 to Fig. 5)
4. Replace the faulty load.
3 Year Guarantee
In the unlikely event of this product becoming faulty due to defective
material or manufacture within 3 years of the date of purchase, please
return it to your supplier in the first year with proof of purchase and it will
be replaced free of charge. For years 2 and 3 or any difficulty in the first year
telephone the helpline on
020 8450 0515.
HELPLINE
020-8450-0515
or email helpline@timeguard.com
For a product brochure please contact:
Timeguard Ltd.
020-8452-1112
or email csc@timeguard.com
A
Group company
67-058-277 (Iss. 5)
For assistance with the product please contact:
Fig. 14
3.28.020620467010
3