The lock mode prevails over single and free access mode. It means that access can be locked
at any time, thus, if within the blade closing area there is no any obstacle they will be closed. The
controller will be in this mode until arrival of command "CANCELLATION OF ACCESS LOCK"
via interface RS-485 from control panel.
Fig. 8
–
Appearance and configuration of controller AUIA.206.21.20.00
"ALARM"
The turnstile switches to this mode from any above mentioned mode in case of unauthorized
access attempts. In this case red LED is frequently blinking (4 times per second), siren alarm is
generated on control panel and output "OUT5" is activated on the controller board. If the turnstile
was opened, then blades would be closed if there were no obstacles in the closing area. The turnstile
will return to the mode preceding the "ALARM" mode as soon as causes of this mode disappear. In
this case the output "OUT5" will go to passive state, siren alarms on control panel will be off and
blades and light indication will be set according to the current mode.
The purpose of the controller contacts intended for connection to peripherals is specified in
Table 5.
1 - ON - when command is issued, the turnstile will
open for 5 seconds;
- OFF - when command is issued, the turnstile will
open for the time set in ACS;
2
-
ON
-
Outputs OUT1
-
5 will be NC;
-
OFF
-
Outputs OUT1
-
5 will be NO;
3
-
5
-
Not usable;
6
-
Free access mode setting when blades are normally
closed is possible by closing IN1 and IN2. Signal on
IN1 or IN2 must be more than 6500 ms to set free
access;
-
ON
-
Activation of free access mode when blades
are normally closed;
-
OFF
-
Deactivation of free access mode when blades
are normally closed;
7
-
ON
-
Activation of free access mode A when blades
are normally closed;
Blades will be open when the first IR sensor is
crossed;
-
OFF
-
Deactivation of free access mode A when
blades are normally closed;
Blades will be open all the time;
8
-
ON
-
Activation of free access mode B when blades
are normally closed;
Blades will be open when the first IR sensor is crossed;
-
OFF
-
Deactivation of free access mode B when
blades are normally closed;
Blades will be open all the time;