23
Commissioning
Controls
The fan speeds of the Titon HRV
Q Plus
will require adjustment to ensure the flow
rates achieved provide adequate ventilation. The Titon HRV
Q Plus
has 2 standard
fan speed settings Continuous Speed and Boost Speed.
The Continuous Speed and Boost Speed are programmed by placing the controller
into Program Mode via the Program/Run Switch and changing the position of rotary
potentiometers.
When applying power for the first time, the unit can take up to four minutes to start
operating.
Prior to the first commission set Continuous Speed potentiometers to minimum
and Boost Speed potentiometers to maximum or reset the controller.
Control Parameters
The Boost Speed cannot be set lower than the Continuous Speed.
The Continuous Speed cannot be set higher than the Boost Speed.
All switching inputs are disabled when the Program/Run Switch is in
Continuous or Boost positions.
Speed control potentiometers are disabled when the Program/Run switch is in
centre Run position.
Boost
Overrun
Timer
Program
Switch
Run
Continuous
Boost
Boost Overrun Timer
Extract
Supply
Potentiometers
Extract
Supply
BP
40262/099
Thermostat
Switch
Boost
Switch
Setback
Switch
Input
Temp
Boost
Cont
1
2
3
4
5
6
7
8
0
60
30
Control Identification
Boost
Overrun
Timer
Program
Switch
Run
Continuous
Boost
Boost Overrun Timer
Extract
Supply
Potentiometers
Extract
Supply
BP
40262/099
Boost
Cont
1
2
3
4
5
6
7
8
0
60
30
DO 4937 iss 01
Summary of Contents for auralite TP518
Page 21: ...21 Wiring Diagrams ...
Page 22: ...22 Notes ...
Page 30: ...30 Service Record Serviced By Company Date Notes ...