Summer Bypass
Summer Bypass is designed to operate during hot periods where fresh air can be
vented straight into the property without being preheated by the extracted stale
air. Summer Bypass operation is automatically controlled. The Summer Bypass
mechanism diverts the stale air being extracted from the dwelling around the heat
cell so that its heat energy is not transferred to the fresh air being supplied to the
property.
Automatic Frost Protection
During very cold weather, Automatic Frost Protection will detect temperatures that
could form ice inside the unit. It will reduce the supply ventilation rate to prevent
ice build up within the heat cell. Automatic Frost Protection reduces the flow rate of
cold air, thus allowing the warmer stale air to raise the temperature within the heat
cell to such a level that prevents the formation of ice. As internal temperatures rise
Automatic Frost Protection will increase the supply ventilation flow rate back to the
commissioned settings.
Summer Mode
In properties where it is desirable to reduce the supply of warm fresh air during hot
weather, but where full Summer Bypass may be inappropriate or not available, the
optional Summer Mode operation is available. Summer Mode operates by stopping
the supply fan. Summer Mode can be triggered either manually or automatically:
Manual - This is by means of a volt-free switch wired directly into the controller PCB
Automatic - This is by means of a dedicated wall mounted room thermostat. In
this configuration Summer Mode will only operate when the temperature within
the room has exceeded the dedicated thermostat setting. When Summer Mode is
selected the supply fan will remain off even if the HRV is placed into Boost.
Summer Mode must not be installed in dwellings where open flue combustion
appliances are used. Summer Mode must not be installed on HRV
Q Plus
MB units.