TP302HA, TP303HA, TP312HA & TP313HA
The fan speeds of the Titon CME2 & 2.1
Q Plus
will require adjustment to ensure that
the flow rates achieved provide adequate ventilation. The Titon CME2 & 2.1
Q Plus
has 3 standard fan speed settings, Continuous Speed, Boost Speed and Setback
Speed.
All speeds are adjustable via Rotary Potentiometers.
Control Parameters
All volt-free switch inputs are disabled when the Program / Run Header Link is
in the Program position.
All speed control potentiometers are disabled when the Program / Run Header
Link is in the Run position.
Boost Overrun Timer & Humidity Sensor adjustment can be done at any time
without the need to move the Program / Run Header Link
The unit needs to be powered up for the commissioning settings to be stored.
Continuous Speed
Boost Speed
Humidity Sensor
Boost Overrun Timer
Program / Run
Header Link
Setback Speed
1
2
3
4
5
6
7
8
0
30
15
55%
85%
70%
Continuous Speed
Boost Speed
Humidity Sensor
Boost Overrun Timer
Program / Run
Header Link
Setback Speed
1
2
3
4
5
6
7
8
0
30
15
55%
85%
70%