background image

DIAGRAM C

DIAGRAM D

LEVEL AND MARK A
LINE BETWEEN STUDS
WHERE DIFFUSER IS
TO BE INSTALLED.

CAREFULLY MAKE A LEVEL
HORIZONTAL CUT IN SHEET-
ROCK BETWEEN STUDS NO
LONGER THAN 13 5/8”.

• The AireShare™ is for general ventilating use only. Do not use to exhaust hazardous or explosive 

materials or vapors.

•  The AireShare™ may not be installed in a ceiling.

•  The AireShare™ may not be installed in an outside wall.

•  The AireShare™ may not be installed in a wall rated as a “fire wall.”

•  The AireShare™ may not be used to move air from one floor (story) to another floor.

•  The AireShare™ may not be used to move moisture-laden air from sources such as bathrooms 

and kitchens. (Ne pas installer pres d'un apparel.)

•  The AireShare™ may not be used in a window. (Ne pas utilliser dans une penetre.)

WARNING:

To reduce the risk of fire, electrical shock and injury to persons, the AireShare™ must 

be installed with the Diffuser that was provided. Do not use this product with any Diffuser other than 
the AS2 Diffuser.

WARNING:

To reduce the risk of fire or electrical shock, do not use this fan with any solid state speed

control devices. (

Avertissment:

Ne Convient pas a Des Regulaters De Vitesse a Semi-Conducteurs.)

Disrupt power at circuit breaker to outlets and switches within the stud wall you will be working. 

BEFORE YOU START:

Determine the stud wall section that you want to use to mount the Blower and Diffuser. It may be preferable to select a stud wall section
that contains an electrical outlet for wiring. 

IMPORTANT: Wall studs must be spaced a minimum of 16” o.c., (See Diagram A). 

Mark

inside edges of studs the Aireshare

TM

will be installed between and verify there is at least 14” between the inside edges. Slide a stud

finder down the wall between the studs to help verify the stud wall cavity is completely open, (See Diagram B).

TOOLS REQUIRED

Hand Sheetrock Saw 

Phillips & Straight Screwdrivers      Level   

Tape Measure       Utility Knife or Scissors

Wire Stripper

INSTALLING DISCHARGE DIFFUSER

WARNING:

Disrupt power at circuit breaker to outlets and switches within the stud wall you will be working. When sawing through

sheetrock you must stop if you detect the saw blade coming in contact with any wiring or plumbing. Investigate further to determine 
if it is possible to safely continue to use this wall cavity space. Switch to another stud wall cavity if necessary.

NOTE:

Typical installations will have the Diffuser high and the Blower low, but there may be instances where it 
is desirable to have the Blower mounted high and the Diffuser low to take air from the ceiling level.

IMPORTANT:

Install Diffuser first if mounting the Blower down low and the Diffuser high so sheetrock from the

Diffuser cut out does not fall into wall cavity and damage Blower. Install the Blower first if mounting the Blower high
and Diffuser low so sheetrock from the Blower cut out does not fall into wall cavity and damage Diffuser.

1. Determine if you would like a high or low discharge. The Diffuser may be mounted as close as 3" above the top 

of Blower cut out opening or as close as 3" to the ceiling. 

2. Level and mark a line between studs where you want the top of the Diffuser, (See Diagram C)  

3. Using a hand sheetrock saw carefully make a horizontal cut along the line. Cut the sheetrock completely until you 

come in contact with the opposite stud. 

NOTE:

If studs are spaced greater than 16” o.c., the horizontal cut line 

should not exceed 13 5/8”, (See Diagram D).

DIAGRAM A

Wall studs must be

spaced a minimum 

of 16” o.c.

IMPORTANT: Wall cavity
between studs must be com-
pletely open between Blower
Intake and Diffuser

DIAGRAM B

Wall studs must

be spaced a

minimum 

of 16” o.c.

BLOWER 

OPENING

DIFFUSER

IMPORTANT:
Wall cavity
between studs
must be com-
pletely open
between
Blower intake
and Diffuser

WARNING

!

WARNING

!

Summary of Contents for AIRESHARE AS2

Page 1: ...roper AireShare performance AireShare CFM x 60 L x W x H of target room ACH NOTE Aireshare CFM is 110 on High 95 on Med and 80 on Low 3 4 Air Changes hour ACH recommended for best temperature equalization 4 5 Air Changes hour ACH recommended for rooms with high cooling or heating loads Examples include rooms with extensive out side walls windows over tuck under garages or in extreme climates More ...

Page 2: ...y open See Diagram B TOOLS REQUIRED Hand Sheetrock Saw Phillips Straight Screwdrivers Level Tape Measure Utility Knife or Scissors Wire Stripper INSTALLING DISCHARGE DIFFUSER WARNING Disrupt power at circuit breaker to outlets and switches within the stud wall you will be working When sawing through sheetrock you must stop if you detect the saw blade coming in contact with any wiring or plumbing I...

Page 3: ...mark the grille position through the two mounting holes IMPORTANT Make sure Intake Grille flanges do not interfere with baseboards outlets If Intake Grille is mounted up high towards the ceiling the top flange must be mounted 1 below the ceiling so Intake Grille top opening clears double plate at top of stud walls See Diagram H 3 Mark a level line 3 5 8 straight above and below each Intake Grille ...

Page 4: ...ired to the brown motor lead If wiring into a switched 120 VAC power source follow the AS2 connection diagram below If using the optional FC24 Fan Center to control the Aireshare by a 24 volt thermostat follow the FC24 wiring diagrams CAP 2 5 uF CAP 6 uF CAP 5 uF 8089034 10 27 14 MOTOR AS2 BLOWER AS2 ELECTRICAL BOX CABLE L1 60 Hz 120 VAC N GROUND BLK GRN WIRE NUTS BY OTHERS SUPPLIED BLK BRN GRN YE...

Page 5: ... G R N Y E L B R N T STAT WIRING SEE FC24 B L K BLK GRN WIRE NUTS BY OTHERS SUPPLIED L1 HIGH SPEED AS2 BLACK LEAD CAP 6 uF CAP 5 uF L1 MED SPEED L1 LOW SPEED AS2 BLACK LEAD AS2 BLACK LEAD A 2 5 uF CAPACITOR IS ALWAYS USED ON THE 120 VAC N LEAD AND IS WIRED BETWEEN THE WHITE AND BROWN LEADS OF THE MOTOR NOTE OR OR AS2 SPEED OPTIONS BELOW AIRESHARETM MODEL AS2 WIRING CONNECTIONS WITH THE OPTIONAL FC...

Page 6: ...A 120 24 YEL VIO GRY BLK 8089031 9 4 14 FC24 7 8 3 6 R WALL THERMOSTAT NO C TERMINAL 24 VAC WIRE LEGEND 24 VAC 120 VAC BY OTHERS RED YEL BLK WHT XFORMER 20 VA 120 24 YEL VIO GRY BLK FC24 7 8 3 6 G W Y R WALL THERMOSTAT WITH C TERMINAL 24 VAC C WIRE LEGEND 24 VAC 120 VAC BY OTHERS FC24 T STAT WIRING G W Y 120 VAC WIRING AS1 AS2 SEE 120 VAC WIRING AS1 AS2 SEE FAN ON HEAT COOL G W Y FAN RUNS CONSTANT...

Reviews: