2. Attach speed clips to vent pipe and align with four holes drilled in step 1.

3. Insert DUCT BOOSTER

®

in the slot with the adjustable damper curved plate 

above blower wheel pointing in the direction of air flow.  The front flange goes
inside the duct and the side flanges go on the outside.  Bend the flanges to 
conform to the duct.  Secure DUCT BOOSTER® to duct utilizing speed clips 
and screws provided.  Use wrench to tighten nut behind electrical box.

INSTALLATION RESTRICTIONS

Do not install the  DUCT BOOSTER® where temperatures of air within the duct
exceed 200

O

F.  This temperature would only rarely be found on a forced warm

air system but could exist close to the furnace on a gravity warm air system.
Locating the DUCT BOOSTER®  near the outlet end of a duct will provide the
most efficient performance.

The  DUCT BOOSTER® must be installed with the motor shaft horizontal.  It
can be installed on the bottom or top of a horizontal duct or any side of a 
vertical duct.

CAUTIONS

1. Failure to install, maintain and/or operate the DUCT BOOSTER®  in accor-

dance with manufacturer’s instructions may result in conditions which can 
produce bodily injury and property damage.

2. Disconnect power supply when making wiring connections and servicing the 

DUCT BOOSTER®.  Failure to do so may result in personal injury and/or 
equipment damage.

3. Make certain the power source is adequate for the DUCT BOOSTER®  

requirements.

ADJUSTMENT OF VARI-DRAFT DAMPER

The DUCT BOOSTER® is shipped from the factory so that the maximum CFM
is established when unit is installed.  To reduce the CFM, slide the Vari-Draft
damper so it will penetrate into duct further.  Adjustments should be made prior
to installing the DUCT BOOSTER®  into duct.

Summary of Contents for DB-2 DUCT BOOSTER 8504030 REV B 0900

Page 1: ...OR CONSEQUENTIAL DAMAGES ARISING FROM THE USE OF THIS PRODUCT THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS WARRANTIES AND NO AGENT IS AUTHORIZED TO ASSUME FOR US ANY LIABILITY ADDI TIONAL TO THOSE SET FORTH IN THIS LIMITED WARRANTY IMPLIED WARRANTIES ARE LIMITED TO THE STATED DURATION OF THIS LIMITED WARRANTY Some states do not allow limitation on how long an implied war ranty lasts so that limit...

Page 2: ...DUCT BOOSTER into duct This will allow screws to better align with the speed clips provided 1 Opening should be cut in the bottom or top of a horizontal duct or any side of a vertical duct The motor shaft will then be in the horizontal position Apply the mounting template provided to the duct cut opening and drill four 5 16 holes noted on template WIRING DUCT BOOSTER IN PARALLEL WITH HEAT CYCLE OR...

Page 3: ...of a duct will provide the most efficient performance The DUCT BOOSTER must be installed with the motor shaft horizontal It can be installed on the bottom or top of a horizontal duct or any side of a vertical duct CAUTIONS 1 Failure to install maintain and or operate the DUCT BOOSTER in accor dance with manufacturer s instructions may result in conditions which can produce bodily injury and proper...

Page 4: ... will short out the blower motor A The gas or oil fired central furnace may include refrigerant cooling coils however it must be equipped with 120 VAC single phase blower motors The DUCT BOOSTER SHOULD NOT BE WIRED IN PARALLEL WITH 240 VAC BLOWER MOTORS B The basic furnace wiring and components should not be disturbed except for wiring interconnection of the DUCT BOOSTER and furnace blower motor a...

Reviews: